Compatible Loop Devices and Panel Responses


The following table shows all devices compatible with the panel. It shows the panel’s response to events from each device type, and indicates the change in
analogue value and input bits that will be displayed in the status mode. Note that some device types automatically receive cause effect outputs by default. Any such
programming is indicated in the default cause and effect column.

Device type

Type
Code

Condition Panel

response

Analogue Value

Status bits
(210)

Output bits

Default cause
and effect

Comments

CEL sounder
controller

1 Quiescent

Input 1 operated
Input 2 operated
Input 3 operated
Circuit fault

None
Mode 1
Mode 2
Remote fault
Remote fault

AV = 16
AV = 64
AV = 48
AV = 4
AV = 4

000
000
000
000
000

0 = evacuate
1 = alert
2 = relay

Bit 0 set on
evacuate

CEL Loop
powered sounder

1 Quiescent

Fault

None
Remote fault

AV = 16
AV = 4

Echo
output bits

0 = evacuate
1 = alert
2 = not used

Bit 0 set on
evacuate

Series 90
sounder/ sounder
controller

1 Quiescent

Circuit fault or fault
input operated

None
Remote fault

AV = 16
AV = 4

Echo
output bits

0 = evacuate
1 = alert
2 = not used

Bit 0 set on
evacuate

XP95 sounder/
sounder
controller

1 Quiescent

Circuit fault

None
Remote fault

AV = 16
AV = 4

Echo
output bits

0 = evacuate
1 = alert
2 = not used

Bit 0 set on
evacuate

CEL I/O unit

2

Quiescent
Input 1 operated
Input 2 operated
Input 3 operated or
power supply failed

None
Fire
Input
Remote fault

AV = 16
AV = 64
AV = 48
AV = 4

000
000
000
000

0 = relay 1
1 = relay 2
2 = relay 3

Series 90 3-way
I/O unit

2 Quiescent

Input 1 operated
Input 2 operated
Input 3 operated

None
Fire
Input
Remote fault

AV = 16
AV = 16
AV = 16
AV = 16

000
1XX
01X
001

0 = relay 1
1 = relay 2
2 = relay 3

X

means

status

does not affect
panel status