Document Ref: Nex8inst.doc/Rev0 09.07.00

Page 27 of 30

Originator MC Checked by AC__

Device type

Type
Code

Condition Panel

response

Analogue Value

Status bits
(210)

Output bits

Default cause
and effect

Comments

Series 90 3-way
I/O analogue unit

2 Quiescent

Input 1 operated
Input 2 operated
Input 3 operated

None
Fire
Input
Remote fault

AV = 8 to 44
AV = 55 to 127
AV = 45 to 54
AV = 0 to 7

000
1XX
01X
001

0 = relay 1
1 = relay 2
2 = relay 3

X

means

status

does not affect
panel status.
See note 2.

Series 90 1-way
I/O unit

2 Quiescent

Input operated

None
Fire

AV = 16
AV = 16

000
001

0 = relay
1 = not used
2 = not used

Series 90 switch
monitor unit

2 Quiescent

Input operated

None
Fire

AV = 16
AV = 16

000
100

0 = remote
indicator
1 = not used
2 = not used

XP95 I/O unit

2

Quiescent
Input operated
Opto input active
Input fault

None
Fire
Input
Remote fault

AV = 16
AV = 16
AV = 16
AV = 4

000
1X0
010
000

0 = remote
indicator
1 = not used
2 = not used

Fire

overrides

input which in
turn overrides
remote fault

XP95 output unit 2

Quiescent

None

AV = 16

000

0 = relay

Series 90
ionisation smoke

3 Quiescent

Fire
Alert
Fault

None
Fire
Alert
Data fault

AV = 8 to 44
AV = 55 to 127
AV = 45 to 54
AV = 0 to 7

Echo
output bits

0 = remote LED
1 = self test
2 = LED

Bit 0 and bit 2
set when device
is in fire

See note 1.

XP95 ionisation
smoke

3 Quiescent

Fire
Alert
Fault

None
Fire
Alert
Data fault

AV = 8 to 44
AV = 55 to 127
AV = 45 to 54
AV = 0 to 7

Echo
output bits

0 = remote LED
1 = self test
2 = LED

Bit 0 and bit 2
set when device
is in fire

See note 1.

CEL zone
monitor

4 Quiescent

Input 1 operated
Input 2 operated
Input 3 operated

None
Fire
Alert
Remote fault

AV = 16
AV = 64
AV = 48
AV = 4

000
000
000
000

0 = relay 1
1 = relay 2
2 = relay 3

Bit 0 set on
reset or clear
faults