Figure 44. Gas Direct Ignition Furnace, Heating & A/C Ready - All M1M Models

Steady ON

Control OK

Steady ON

Good Flame Signal

Steady OFF

N

o power

Blinking

Weak Flame Signal

Rapid Flash

False flame or internal control fault

Steady OFF

No Flame Signal

1 Flash

Limit switch is open

2 Flashes

Pressure switch is open with inducer on

3 Flashes

Pressure switch is closed with inducer off

4 Flashes

Lockout due to failed ignition

5 Flashes

115 vac & neutral reversed or no ground

1.

Incoming power must be polarized. Observe color

coding. (See furnace data label for electrical

information.)

2.

If any of the original wires (as supplied with the

appliance) must be replaced, use 105˚C Thermoplastic

type wire or its equivalent.

WIRING DIAGRAM