Set MODBUS
parity *

Change the humidifier controller’s
MODBUS parity.
Range is None, Even, Odd
This setting shall be non-volatile with a
default setting of Even.

40554

The value changes will only take
effect following a hardware reset
of the control board

Reset Run
Hour Counter

Resets the humidifier controller’s run
hour counter to zero hours

40560

255 will start the run hours
counter process.
0 will be accepted to clear the run
hours counter.

Current
damping

Buffers the measured current

40910

From 0 to maximum (depending
on software ability)

Electrode
current

The value of the electrode current in
Amps

30850

Hex value representing the
humidifies current in amps
Resolution: 0.10 amps
Example:
015F (hex) = 35.1 Amps

Steam output

The current steam output in Kg/Hr. or
LBS/hr

See UNITS (Modbus 40031)

30860

Hex value representing the
humidifies steam output in kg/hr
Resolution: 0.10 kg or LBS
Example:
013B (hex) = 31.5 kg/hr or
LBS/hr

Run hour
counter

The number of hours the humidifier
has been in operation since the last
time the run hour counter was reset

30414

Hex value representing the
number of humidifier operational
hours since the last reset.
Resolution: 5 minutes
Maximum count: 5460 Hours.
Example:
07D0 = 2000 hours

Firmware
version

The firmware version of the humidifier
controller

30361

Packed BCD version 3.52 would
be 0x0352

Humidifier state

Describes the current state of the
humidifier and it’s I/O’s
Contactor ON/OFF
Fill Valve ON/OFF
Drain Valve ON/OFF

30800

Bit Allocation
Note More than one bit can be
active at any time.
Contactor on = 1
Fill valve on = 2
Drain valve on = 4