Installing the new cylinder, Maintenance, Extended shutdown – Nortec Industries None User Manual

Page 6: Troubleshooting, Terms used, 3ш 1ш

Advertising
background image

dependent on water supply conditions and humidifier
usage. Failure to replace the cylinder at the end of
cylinder life may result in unit damage. NORTEC is not
responsible for any damages resulting from, or
attributable to, the failure to replace a used cylinder
(see Manufacturer’s Warranty).

REMOVING THE OLD CYLINDER

n

See Figure # 5.

1. Turn off the water supply to unit.

2. The old cylinder must be drained completely

before removing. This is done by pushing the
auto on/off/drain switch to the “drain” position.

3. When completely drained, push the auto

on/off/drain switch to the “off” position.

4. Open the main disconnect during the entire

cylinder change operation.

5. The power wires to the cylinder are attached

by cylinder plugs to the electrode pins on top of
the cylinder. Pull these plugs vertically off the
pins. See Figure # 5.

6. Using slot screwdriver, loosen the steam hose

clamp(s) and pull steam hose off vertically.

7. The cylinder is now ready to be lifted out of the

unit.

INSTALLING THE NEW CYLINDER

1. The reverse procedure should be followed to

install a new cylinder. The main disconnect is
to be left open until the cylinder is completely
installed and reconnected.

2. Ensure that the cylinder mounting stubs are

seated properly in the allotted side mounting
slots within the unit.

3. The white sensor plug on all units is for the

sensor pin, which always goes on the single
pin offset from the others. See Figure # 6.

4. Ensure that cylinder plugs are very snug on

the pins.

5. Replace loose fitting plugs, loose plugs may

generate enough heat to melt and destroy the
plug and new cylinder plugs must be ordered.

MAINTENANCE

WARNING! The plumbing and electrical

compartments contain high voltage components and
wiring. The access cover is attached with screws.
Access should be limited to authorized personnel
only.

EXTENDED SHUTDOWN

Before disconnecting power to the humidifier for a

period of extended shutdown, ALWAYS DRAIN the
cylinder first. Otherwise, the electrodes are subject to
harmful corrosion which drastically shortens the
cylinder life. Do NOT leave the switch in the DRAIN
position indefinitely as the drain coil could burn out.
Leave the switch in the OFF position and “open” the
main external fused disconnect to stop power to the
humidifier. Close the shut off valve in the water
supply line feeding the humidifier.

TROUBLESHOOTING

TERMS USED

F.L.A. (Full Load Amps): Refers to amps listed on

the humidifier specification label.

SHORT CYCLING: When the ‘on time’ of the

humidifier is less than ten minutes upon a call for
humidity. To correct short cycling, all humidifiers have
a capacity adjustment which allows the output of the
humidifier to be reduced to as low as 20% of rated
output, thus extending the ‘on time’ required to
maintain output.

- 4 -

Cylinder
Plug

Cylinder Pin

Cylinder Pin

Cylinder Pin

Cylinder Pin

Cylinder Pin

White
Sensor Plug

Sensor Pin

Sensor Pin

Figure #6

Plugs