- 10 -

Maximum
production

The rated maximum steam production
for the humidifier

30802

Value written into Unit type
(40600) is also stored here

Alarms

The humidifier shall describe any faults
Too long to fill
Excess Current
End of cylinder life
No current

30364

Bit Allocation
Note More than one bit can be
active at any time.
Too long to fill = 1
Excess current = 2
End of cylinder life = 4
No Current = 8

Units

Required by the control board for
capacity calculations

40031

0: 0-1. 0=LBS, 1=KG

Unit type

Required by the control board for
current and capacity calculations

406000

Depending on the setting in
UNITS (Modbus: 40031)
Hex value representing
maximum unit capacity (100% fill
off amps)

Unit voltage

Required by the control board for
current and capacity calculations

40610

Format is Hexadecimal

numeration table (see below)

Hex

Value

Unit

Type

0

110-

120

1

208

2

220-

240

3

230

4

277

5

347

6

380

7

400

8

415

9

440-

480

A

550-

600

Unit phase

Required by the control board for
current and capacity calculations.

40620

Bit Allocation
Single phase = 1
Three phase = 2
Three phase (6 electrode) = 4