Nortec 132-3091 User Manual

Page 15

Advertising
background image

- 12 -

NHMC

UNIT STATUS LAMPS

REMOTE INDICATION (24 VAC TO:)

SYSTEM MESSAGE

DISPLAYED ON LCD

UNIT

CONTACTOR YELLOW

GREEN

61-20

“YELLOW”

62-40

“GREEN”

63-36

“RED”

Maximal Level

ON

ON

ON

OFF

ON

OFF

Excess Current / Error 1

OFF

ON

OFF

ON

OFF

OFF

No Current / Error 2*

OFF

ON

OFF

ON

OFF

OFF

Max. Filling Time / Error 3

OFF

ON

OFF

ON

OFF

OFF

Cylinder Spent / Error 4

ON

ON

ON

OFF

ON

ON

No Current / Error 5

OFF

ON

OFF

ON

OFF

OFF

Output Too Low / Error 6

OFF

ON

OFF

ON

OFF

OFF

Electronic / Error 7

OFF

ON

OFF

ON

OFF

OFF

Phase Interrupt / Error 8

ON

ON

OFF

OFF

OFF

OFF

Cyl. Lifespan End / Error 9

OFF

ON

OFF

ON

OFF

ON

* When No Current/Error 2 is displayed, display will change to show Maximal Level and will alternate back and forth.

NHP

UNIT STATUS LAMPS

REMOTE INDICATION

(24 VAC TO:)

SYSTEM FAULTS*

UNIT CONTACTOR

YELLOW

GREEN

“YELLOW” 61-20

Maximal Level

See NHMC Chart above for details

Excess Current

OFF

ON

OFF

ON

No Current

OFF

ON

OFF

OFF

Max. Filling Time

OFF

ON

OFF

ON

Cylinder Spent

ON

FLASHING

ON

OFF

No Current

OFF

ON

OFF

OFF

Output Too Low

OFF

ON

OFF

OFF

Electronic

N/A

N/A

N/A

N/A

Phase Interrupt

N/A

N/A

N/A

N/A

Cyl. Lifespan End

OFF

FLASHING

OFF

ON

*NOTE: NHP does not display actual message or error.

- Remote indication 61-20 “yellow” means humidifier has shutdown and one of several system messages is showing.

The exception is on the NHP when No Current or Output Too Low is the fault, 61-20 “yellow” will be off, but the yellow
light on the NHP will be on.

- Remote indication 62-40 “green” means contactor is on; humidifier is operating.

- Remote indication 63-36 “red” means cylinder is spent; replacement is necessary.

Figure #13

System Messages and Responses (EPROM : 2.XXN)

Advertising