Lo ca tion & mounting 2, Hu mid i fiers 2, Blower packs 2 – Nortec 132-3091 User Manual

Page 5: Location & mounting humidifiers blower packs, Location & mounting

Advertising
background image

LOCATION & MOUNTING

HUMIDIFIERS

NH Series humidifiers are designed to mount on a

suitable wall or vertical surface. Do not sit on floor due

to clearances required for plumbing, electrical, and

control entrances. The clearance dimensions shown

in this manual are for reference only and are the

minimum required for maintenance of the humidifier.

Local and National Codes should be consulted prior to

final location and installation of the humidifier.

NORTEC can not accept responsibility for installation

code violations.

1.

Location of the humidifier should be below and as

close as possible to the steam distributor location

as possible.

2.

For front and side clearance requirements (for

access during installation, maintenance and

troubleshooting), see Figure #2.

3.

If possible, DO NOT locate humidifier any further

than absolutely necessary from steam distributor

location, as net output will be reduced as a result

of heat loss through steam hose (see Engineering

Manual, Form -163D). Also, increased static

pressure may necessitate using an accessory fill

cup extension kit.

4.

Where possible, mount humidifier at a height

convenient for servicing.

5.

Wall mounting bracket provided should be

securely attached horizontally and open edge

upwards, using field-supplied fasteners. Use a

minimum of 3 - #12 x 3" long wood screws, or

better, into a vertical structural surface. If any

spacer material is used between the bracket and

the structural material such as drywall, increase

fastener length accordingly. In addition, install a

minimum of 2 field supplied fasteners in the holes

provided in the back of the unit to prevent the unit

from being bumped off the wall bracket. See

Figure #3.

6.

Make sure humidifier is level.

7.

DO NOT mount humidifier on hot surfaces.

8.

If humidifiers are mounted on roof, a

thermostatically ventilated weatherproof cabinet by

others should be used. Consult factory.

9.

DO NOT mount humidifiers in an area where

freezing may occur. Use an accessory Low

Temperature Protection Kit, if necessary.

10.

DO NOT mount humidifiers on vibrating surface.

Consult factory.

BLOWER PACKS

1.

Blower packs are an optional accessory used to

directly distribute steam to localized areas (such

as computer rooms) or in structures that do not

have a built-in air distribution system.

2. Blower packs are available integrally-mounted on

humidifier (built-on blower pack, BOBP, see Figure

#4) or detached and field-piped and wired to

humidifier (remote mounted blower pack RMBP,

see Figure #5).

3.

All NH Series blower packs consist of a steel

cabinet containing: blower/motor powered by

voltage directly from the humidifier, fuse, relay,

speed select switch (in NH-050 and larger),

stainless steel steam distributor, supply air grille

with adjustable louvers, and built-in manual reset

- 2 -

Power And

Control

Wiring

Optional

Built-On

Blower Pack

Single

Circuit

Humidifier

Built-In

Supply Air

Grille

Built-In Steam

Distributor

Figure #4

Built On Blower Pack (BOBP)

005-030

7.7 (19.6cm)

050-200

7.7 (19.6cm)

A

WALL

FASTEN WALL BRACKET
(FACTORY SUPPLIED) TO
WALL USING ANCHOR BOLTS
(3) SUPPLIED BY OTHERS

A

7.7”

(19.6 cm)

Fasten wall bracket

(Factory supplied) to

wall using field supplied

fasteners.

Wall

Figure #3

Wall Bracket Mounting Detail

Advertising