Di ag nos tic pro ce dures - trou ble shooting 11, Prin ci ple of op er a tion 12, Fill rate 12 – Nortec Steam Humidifiers User Manual

Page 13: Drain time 12, Diagnostic procedures - troubleshooting

Advertising
background image

3. This color-coding must be adhered to when

replacing cylinder plugs on pins.

4. The electrode plug with the orange wire always

goes on the single pin surrounded by a plastic
shoulder.

5. Ensure that cylinder plugs fit snugly on the pins.

6. If a cylinder plug becomes loose the cylinder

harness must be replaced (P/N 158-1305 see
parts list).

MANDATORY CLEANING OF THE DRAIN

VALVE

Always clean the drain valve before installing a

new cylinder since the valve port may be as dirty as

the used cylinder.

1. Note the ring terminal for drain valve green ground

wire is sandwiched between the drain valve body
and drain pan.

2. Remove the two screws securing drain valve body

to the drain pan. Disconnect the two slip-on
terminals from the two tabs on the (24 Vac) drain
valve coil.

3. Remove the hose clip and hose connection from

drain valve body.

4. The drain valve assembly is now free to be taken

to a sink for disassembly and cleaning.

5. Remove the snap-fit red cap from the coil

assembly and slide coil off the actuator.

6. Loosen the actuator with a wrench and unscrew

from the plastic valve body.

7. Clean the exposed core, spring and plastic drain

valve port.

8. The tapered end of the spring must be installed

toward the solenoid. Reassemble and tighten the
actuator 1/4 turn past hand-tight.

9. Clean out the end of the hose, then reconnect it to

the drain valve body with the clamp.

10. Inspect the o-ring to make sure it is in good

condition.

11. Fit mounting screws through the drain valve body,

one through the ring terminal on green ground
wire.

12. Push the two slip-on terminals back onto the two

tabs on the coil. The terminals, although not
identical, are reversible.

WARNING: To prevent the possibility of electrical

shock the green ground wire must be reinstalled

before power is restored.

EXTENDED SHUTDOWN

Before disconnecting power to the humidifier at

the end of humidification season, ALWAYS DRAIN the

cylinder first. Otherwise, the electrodes are subject to

harmful corrosion which shortens cylinder life. Do

NOT leave the switch in the DRAIN position

indefinitely as the drain coil could burn out. Leave the

switch in the OFF position and “open” the main

external fused disconnect to stop power to the

humidifier. Close the shut off valve in the water supply

line feeding the humidifier. Lock the cabinet door(s) to

prevent unauthorized tampering. All doors are factory

supplied with keyed locks. DO NOT LEAVE THE KEY

IN THE LOCK. ACCESS SHOULD BE LIMITED TO

AUTHORIZED PERSONNEL ONLY.

- 10 -

Advertising