Re mote mount ing the blower pack 4, Plumbing 5, Wa ter supply line 5 – Nortec Steam Humidifiers User Manual

Page 7: Remote mounting the blower pack, Plumbing, Water supply line

Advertising
background image

4. Put the power leads from the blower pack through

this opening as you position the blower pack on
top of the RESDELUX humidifier

5. Push the blower pack forward until the locating

tabs on the bottom of the blower pack with slots in
the top of the RESDELUX push forward to engage.

6. Use two Phillips screws with star washers in the

Blower Pack screw support tabs to secure to the
RESDELUX unit.

7. Remove the front door and service cover from the

RESDELUX humidifier.

8. Connect the power leads for the blower pack to

terminal P7 on the RESDELUX control board
located next to the capacity adjustment
potentiometer.

9. Use the short piece of steam hose and hose

clamps supplied with the basic hardware kit to
connect the steam cylinder to the blower pack
steam distributor.

Installation of the blower pack is now complete.

For instructions on mounting the RESDELUX

humidifier please see the location and mounting

section.

Remote Mounting of the Blower Pack

1. The remote mounted blower pack should be

located at least 7’ off the floor to prevent the
discharged steam from coming in contact with
pedestrian traffic or any obstruction.

2. When installing the remote blower pack, ensure

the primary voltage to the RESDELUX has been

switched off at the electrical panel, or that it is
unplugged (RESDELUX/C).

3. Find a suitable location for mounting the remote

blower pack. The surface should be flat with
adequate clearances for the top, side, and front

:

4. Minimum slope of steam hose is 20°. Steam lines

longer than 5 ft require condensate trap installation
(see Figure #6).

5. RESDELUX blower pack has two teardrop (or

keyhole) openings on the back of the cabinet for
mounting purposes. They are located 8 ¼” apart,
and 1” from the top of the blower pack cabinet.

6. Measure the screw locations and use two #8

screws, 2” long. The screws should be anchored in
a standard 2” x 4” wood stud or equivalent to
ensure adequate support of the blower pack and
connecting steam hose.

7. Remove the 7/8” knockout on the top of the

RESDELUX humidifier and insert the closed finger
grommet into the opening.

8. Put the power leads from the blower pack through

this opening. If the wire leads are not long enough
field splice the additional requirement, or get a wire
extension kit (P/N 1502326) available from
NORTEC.

- 4 -

Minimum Ceiling

Clearance

inches (cm)

Minimum Side

Clearance

inches (cm)

Minimum frontal

Clearance

inches (cm)

18” (45)

18” (45)

60” (150)

Table #1

Clearances of Remote Mounted Blower Pack

Figure #9

Blower Pack Cabinet Assembly

Figure #10

Steam Absorption Distances

H

0”

F

W

Steam Output

F

W

H

4 lbs/hr

36"

12"

12"

6 lbs/hr

42"

16"

18"

8 lbs/hr

48"

18"

18"

Steam absorption space size in inches for ambient humidity

30% RH, room temperature and selected steam outputs of

RESDELUX humidifier.