INSTALLATION

RECEIVING & UNPACKING EQUIPMENT

1.

Check packing slip to ensure ALL material has
been delivered.

2.

All material shortages are to be reported to
NORTEC within 48 hours from receipt of goods.
NORTEC assumes no responsibility for any
material shortages beyond this period.

3.

Inspect shipping boxes for damage and note on
shipping waybill accordingly.

4.

After unpacking, inspect equipment for damage
and if damage is found, notify the shipper
promptly.

5.

All NORTEC products are shipped on an F.O.B.
factory basis. Any and all damage, breakage or
loss claims are to be made directly to the
shipping company.

PRE-INSTALLATION CHECKPOINT

1.

Ensure that available voltage and phase
corresponds with humidifier voltage and phase
as indicated on humidifier’s nameplate label.

2.

Ensure that the dedicated external disconnect
switch is of sufficient size to handle the rated
amps as indicated on the nameplate label. Refer
to local codes.

3.

Report any discrepancy immediately.

HUMIDIFIER CONFIGURATION

To avoid any danger, never operate the

humidifier with a door off.

To open the door, use the key to unlock, lift door

up slightly and pull door forward.

LOCATION & MOUNTING

HUMIDIFIERS

RESDELUX Series humidifiers are designed to

mount on a suitable wall or vertical surface. Do not sit

on the floor due to additional clearances required for

plumbing, electrical, and control access holes. The

clearance dimensions shown in this manual are for

reference only and are the minimum required for

maintenance of the humidifier. Local and National

Codes should be consulted prior to final location and

installation of the humidifier. NORTEC does not

accept responsibility for installation code violations.

1.

Location of the humidifier should be below and
as close as possible to the steam distributor
location or blower pack. Net output will be
reduced as a result of heat loss through long
steam hose.

2.

See Figure #2 for front clearance requirements
for access during installation, maintenance and
troubleshooting.

3.

Where possible, mount humidifier at a height
convenient for servicing.

4.

To mount the humidifier use two #8 screws, 2”
long, and secure into a standard 2”X4” wood
stud or equivalent structure.

5.

Make sure humidifier is level.

- 1 -

PowerAnd

Control

Wiring

Drain

Water

Supply

Nameplate

Label

Condensate

Return

Steam

Outlet

Figure #1

RESDELUX Series Humidifier

Wall

Min. 36"

Frontal

Clearance

NOTE: Local and national

codes may deviate. Please

consult applicable codes

for clearance requirements

Figure #2

Clearance Requirements