Installation / initial set-up – North Star M165939J User Manual

Page 18

Advertising
background image

Installation / Initial Set-Up

18

♦ Extension cords may be used to power devices that are located at a

distance from the generator. However, use only UL-listed, outdoor-rated,
grounded extension cords of the proper size. Use Table 2 below to choose
an adequately sized extension cord according to the amperage of the
device being used and the length of the cord.

Table 2











WARNING:
Use of under sized extension cords can cause electric shock,
fire, or damage to connected devices.

♦ All extension and appliance cords must be in good condition and not worn,

bare, frayed, or otherwise damaged.

WARNING:
Use of damaged electric cords can cause electric shock or fire.

Note: If an extension cord becomes hot to the touch, it is overloaded or
damaged and must be replaced.

Northern Tool is NOT responsible for damage or injury resulting from
customer use of inadequate extension cords.

Current/Power

Maximum Extension Cord Length

Amps at

240V

Load

(watts)

#10 Ga.

Cord

#12 Ga.

Cord

#14 Ga.

Cord

#16 Ga.

Cord

10 2400 250' 150' 100' 75'
20 4800

125' 75' 50' 25'

30 7200

60' 35' 25' 10'

40 9600

30' 15' 10' *

50 12000

15'

*

*

*