6. Fault rectification

by the user

No hot water.

No voltage

.

heck fuses in the house installation

.

Fault

Info

Rectification

Table 2

Water heating continues

(

see Table 3

).

Clean and/or descale the outlet fittings

.

No flow rate

.

Dirt or limescale in the perlators in the

fittings or shower heads

.

Service symbol

appears.

No water heating

(

see Table 3

).

Service/maintenance is required

.

Defect

symbol

flashing

.

7. Fault rectification

by the qualified installer

Corrective maintenance urgently required;

inform qualified installer

.

Fault / defect code / Info

Possible cause / defect

Rectification

Table 3

Water heating continues.Maintenance

requirement

.

Service code enquiry.

Service / maintenance required

.

Temperature sensor fault

.

Temperature sensor fault

.

Parasitic current anode fault

.

Communication fault with electronic
„regulator“ and „control unit“ modules

.

Check that connector „X10“ is correctly
fitted

L

.

Inspect temperature sensor.

Check that connector „X10“ is correctly
fitted

L

.

Inspect temperature sensor.

Check that connector „X7“ is correctly
fitted

L

.

Check parasitic current anode and

wiring

.

No water heating

.

Defect code enquiry.

Corrective maintenance urgently required!

Defect symbol

>>

flashing

.

Temperature sensor defective

.

Safety thermal cut-out (STB) actuated

.

Heating element defective

.

Check that connector „X10“ is correctly
fitted

L

.

Inspect temperature sensor

.

Ursache beheben und entriegeln; STB kon-
trollieren ggf. austauschen.

Rectify cause and unlock; inspect STB and if
necessary replace

.

Fill the reservoir with water

.

No water in the reservoir

.

No anode current

.

Check that connector „X7“ is correctly
fitted

L

.

Inspect parasitic current anode

and wiring

.

Replace regulator electronic module

(22).

Service symbol.

Check that connector „X2“ is correctly
fitted on both modules

H

.

Check connection cable and modules

.

Code

Continuous display -
setpoint temperature.

Code

Continuous display -
outlet temperature

.

Code

No anode protection

.

Code

Last preset setpoint values

active. Possibly continuous
display of

.

Code

Continuous display -
setpoint temperature

.

Code

No display of heating
element symbol

.

Code

Running dry protection

.

Restore voltage supply

.

No voltage

.

No display in the control panel

.

No connection to the control unit

.

Control unit defective

.

Check that connector „X2“ is correctly
fitted

H

.

Check control unit (

20

) and if necessary

replace

.

Code

Relay defective

.