If the timer were set as in the above examples, the system would run for 4 hours,
shut off for 2 minutes, run for another 4 hours, shut off for 2 minutes, and so on
and so forth.

NOTE

The humidistat takes precedence over the timer for shutting down the system. If the
humidistat reaches its set point, it will shut the system off regardless of the timer to
prevent over humidifying the space.

(4)

The factory default setting for the timer is 2 minutes of off time (cleaning time) after
every 8 hours of operation. Using settings that result in an off time of less than 10
seconds are not recommended. As well, using settings that result in an on time of
less than 15 minutes are not recommended.

E. SETTING THE SYSTEM FOR NORMAL OPERATION

(1)

Once the start-up and adjustment, and configuration procedures have been
completed the unit is ready to operate normally. The following steps complete the
start-up procedures:

(a)

Close and lock all covers including the control panel covers.

(b)

Tighten the lock nuts on the primary air and water regulators.

(c)

Set the humidistat to the desired level.

(2) The AirFog humidification system is now ready to operate normally.