TempTracker Mod

Raypak’s MVB comes standard with TempTracker Mod. This control can be used for space
heating and hot water supply with six application-specific modes to meet various applica-
tions, including outdoor reset for heating systems. The control monitors and displays inlet
and outlet temperatures on all applications as well as monitor outdoor temperature when
an outdoor reset mode is selected. Only Raypak’s TempTracker Mod allows for a user
definable outdoor reset slope. Boiler adjustable limits prevent over cycling, saving energy
and extending the life of the boiler. Your MVB is never down with a sensor failure thanks
to Raypak’s exclusive TempTracker software. It can operate with as little as one function-
ing sensor, keeping you up and running until service arrives.

• P or PID logic

• 0-10VDC Setpoint/Direct Drive Input

• 4-20ma output

-Standard on MVB Cat. I

• Building management direct control

-Coming soon on MVB Cat. IV

• LCD Display

Cat. I*

84%

85%

Cat. I*

84%

Cat. IV

87%

MVB

Input

Recovery Rates (GPH)

10

20

30

40

50

60

70

80

90

100

110

120

130

140

150

500

5,091

2,545

1,697

1,273

1,018

848

727

636

566

509

463

424

392

364

339

750

7,636

3,818

2,545

1,909

1,527

1,273

1,091

955

848

764

694

636

587

545

509

1100

11,200

5,600

3,733

2,800

2,240

1,867

1,600

1,400

1,244

1,120

1,018

933

862

800

747

1500

15,273

7,636

5,091

3,818

3,055

2,545

2,182

1,909

1,697

1,527

1,388

1,273

1,175

1,091

1018

1999

20,353 10,177

6,784

5,088

4,071

3,392

2,908

2,544

2,261

2,035

1,850

1,850

1,566

1,454

1,357

MVB

Input

Recovery Rates (GPH)

10

20

30

40

50

60

70

80

90

100

110

120

130

140

150

500

5,091

2,545

1,697

1,273

1,018

848

727

636

566

509

463

424

392

364

339

750

7,636

3,818

2,545

1,909

1,527

1,273

1,091

955

848

764

694

636

587

545

509

1045

10,640

5,320

3,547

2,660

2,128

1,773

1,520

1,330

1,182

1,064

967

887

818

760

709

1425

14,682

7,341

4,894

3,670

2,936

2,447

2,097

1,835

1,631

1,468

1,335

1,223

1,129

1,049

979

1900

19,576

9,788

6,525

4,894

3,915

3,263

2,797

2,447

2,175

1,958

1,780

1,631

1,506

1,398

1,305

MVB

Input

Recovery Rates (GPH)

10

20

30

40

50

60

70

80

90

100

110

120

130

140

150

500

5,273

2,636

1,758

1,318

1,055

879

753

659

586

527

479

439

406

377

352

750

7,909

3,955

2,636

1,977

1,582

1,318

1,130

989

879

791

719

659

608

565

527

999

10,535

5,267

3,512

2,634

2,107

1,756

1,505

1,317

1,171

1,053

958

878

810

752

702

1250

13,182

6,591

4,394

3,295

2,636

2,197

1,883

1,648

1,465

1,318

1,198

1,098

1,014

942

879

1500

15,818

7,909

5,273

3,955

3,164

2,636

2,260

1,977

1,758

1,582

1,438

1,318

1,217

1,130

1,055

1750

18,455

9,227

6,152

4,614

3,691

3,076

2,636

2,307

2,051

1,845

1,678

1,538

1,420

1,318

1,230

1999

21,080 10,540

7,027

5,270

4,216

3,513

3,011

2,635

2,342

2,108

1,916

1,757

1,622

1,506

1,405

7