8.11 Outside Combustion Air Supply

IMPORTANT: If the building has a slight negative
pressure or corrosive contaminants, such as
halogenated hydrocarbons, are present in the air, an
outside combustion air supply to the heater is
required. Seal all combustion air pipe joints.

Use of optional outside combustion air is not
recommended with unvented heaters.

The air supply duct may have to be insulated to
prevent condensation on the outer surface. The
outside air terminal must not be more than 1' (31 cm)
above the vent terminal.

8.11.1 Length Requirements

Follow the constraints listed

on Page 36, Section 8.6.

8.11.2 Vertical Outside Air Supply for Single Heater Installation

8.11.3 Horizontal Outside Air Supply for Single Heater Installation

Description

Part Number

Vent Cap 4" (10 cm)

90502300

Band Clamp

(Recommended)

Flex Hose

(Recommended)

Vent Cap

W

all

4" (10 cm)

Single Wall Pipe

Burner

Description

Part Number

Vent Cap 4" (10 cm)

90502300