overall heater condition should be throughly
inspected thoroughly.
NOTE: Gas flow and burner ignition are among the
first things that should be inspected.
Please

see Page 48, Section 11.5 for suggested

items to inspect.

11.5 Maintenance Checklist

Installation Code and Annual Inspections:
All installation and service of ROBERTS GORDON

®

equipment must be performed by a contractor
qualified in the installation and service of equipment
sold and supplied by Roberts-Gordon LLC and
conform to all requirements set forth in the

ROBERTS GORDON

®

manuals and all applicable

governmental authorities pertaining to the
installation, service, operation and labeling of the
equipment.
To help facilitate optimum performance and safety,
Roberts-Gordon LLC recommends that a qualified
contractor conduct, at a minimum, annual
inspections of your ROBERTS GORDON

®

equipment

and perform service where necessary, using only
replacement parts sold and supplied by Roberts-
Gordon LLC.

The Vicinity of the Heater

Do not store or use flammable objects, liquids or vapors near the heater.
Immediately remove these items if they are present.

See Page 5, Section 3.

Vehicles and Other
Objects

Maintain the clearances to combustibles.

Do not hang anything from, or place anything on, the heater.

Make sure nothing is lodged underneath the reflector, in between the tubes or
in the decorative or protective grilles (included with select models).

Immediately remove objects in violation of the clearances to combustibles.

See Page 5, Section 3.

Reflector

Support reflector with reflector hanger and support strap.

Reflector must not touch tube.

Make sure there is no dirt, sagging, cracking or distortion.

Do not operate if there is sagging, cracking or distortion.

Make sure reflectors are correctly overlapped.

See Page 23, Section 6.5.1.

Clean outside surface with a damp cloth.

Vent Pipe

Venting must be intact. Using a flashlight, look for obstructions, cracks on the
pipe, gaps in the sealed areas or corrosion.

The area must be free of dirt and dust.

Remove any carbon deposits or scale using a wire brush.

See Page 35, Section 8.

Outside Air Inlet

Inlet must be intact. Look for obstructions, cracks on the pipe, gaps in the
sealed areas or corrosion.

The area must be free of dirt and dust. Clean and reinstall as required.

Tubes

Make sure there are no cracks.

Make sure tubes are connected and suspended securely.

See Page 14, Section 6.

Make sure there is no sagging, bending or distortion.
Clean or replace as required.

Gas Line

Check for gas leaks.

See Page 41, Section 9.

Burner Observation
Window

Make sure it is clean and free of cracks or holes.

Clean and replace as required.