Non-Standard Tier Configuration

Guidelines for Existing Firmware Versions

Non-Standard tier configurations are those configurations supported by Paragon II, but require special
procedures in order to function properly. These include:

Triangle Configuration

Diamond Configuration

Redundant Configuration

When a Non-Standard tier configuration is detected, Paragon will do the following:

Display the message “Illegal Connect/Check CTxxxxxx” on the LCD panel, where CTxxxxxx is
the serial number of UMT that has the Non-Standard configuration on its user ports

Stop normal function and continue displaying the message until the connection is removed and the
unit is reset

While the UMT is trapped on the message, it will send the broadcasting message to all UST1s
every two (2) seconds, “Illegal connection on CTxxxxxx

The message will also appear on the OSD until the Non-Standard tier configuration is removed

Recovery:

After any re-connection subsequent to the Non-Standard tier configuration, all UMT Matrix
Switches should undergo a FUNC reset to clear the switch database. This procedure should be
performed starting from the third tier device down to the base unit.

Whenever a third tier UMT Matrix Switch is replaced, all of the second tier and base UMT Matrix
Switches should undergo a FUNC reset.

Whenever a second tier UMT Matrix Switch is replaced, all of the base UMT Matrix Switches
should undergo a FUNC reset.

Whenever a base UMT Matrix Switch is replaced, only the new UMT Matrix Switch should
undergo a FUNC reset.