Installation, Exterior vent terminal locations – Regency Ultimate U39-LP1 User Manual

Page 9

Advertising
background image

Regency

®

U39 ULTIMATE Direct Vent Freestanding Gas Stove

9

EXTERIOR VENT TERMINAL LOCATIONS

A

=

Clearance above grade, veranda, porch, deck, or balcony *(min.

12"/30cm)

B=

Clearance to window or door that may be opened *(12"/30cm)

C=

Clearance to permanently closed window *(min. 12"/30cm)

D=

V

ertical clearance to ventilated soffi

t located above the terminal within a

horizontal distance of (24"/60cm) from the centerline of the terminal (min.

18"/46cm) check with local code.

E=

Clearance to unventilated soffi

t

(min.

12"/30cm)

F=

Clearance to outside corner: with

AstroCap

T

e

rmination Cap (min. 6"/15cm),

with Dura-V

ent termination cap (min. 12"/30cm)

G= Clearance

to

inside

corner:

with

AstroCap

T

e

rmination Cap (min. 6"/15cm),

with Dura-V

ent termination cap (min. 12"/30cm)

H=

Not to be installed above a meter/regulator assembly within (3'/90cm)

horizontally from the centerline of the regulator

.

J=

Clearance to service regulator vent outlet *(min. 36"/90cm)

K=

Clearance to non-mechanical air supply inlet to building or the combustion

air inlet to any other appliance *(12"/30cm)

L=

Clearance to a mechanical air supply inlet *(min. 72"/1.8m)

M=

**Clearance above paved sidewalk or a paved driveway located on public

property *(min. 84"/2.1m)

N=

Clearance under veranda, porch, deck, or balcony *(min. 12"/30cm)***

Note: *

As specifi

ed in CGA

B149 Installation Code. Note: Local codes or regulations may require dif

ferent clearances.

**A

vent shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings a

nd serves both dwellings.