Warning, 32 step 8.8 classic cast-iron components – Roberts Gorden CoRayVac CRV-B-6 User Manual

Page 38

Advertising
background image

CRV-S

ERIES

I

NSTALLATION

, O

PERATION

AND

S

ERVICE

M

ANUAL

32

Step 8.8 Classic Cast-Iron Components

Schedule 40 Steel Pipe

Cast-Iron Combustion

Chamber

Cast-Iron Adapter

End Vent Plate for

End Burner Only

Cast-Iron Adapter

Coupling

4" Tube

7' (2.13 m) Maximum

Cast-Iron Combustion Chamber

with Schedule 40 Steel Pipe

The total weight of each burner and

combustion chamber is 40.25 lbs (18 kg).

4" Schedule 40 pipe weighs 10.9 lbs.

(5 kg) per foot.

Cast-Iron Combustion Chamber with

Standard 4" O.D. Infrared Tubing

The total weight of each burner and

combustion chamber is 40.25 lbs (18 kg).

4" O.D. 16 Ga. tubing weighs 2.8 lbs.

(1.3 kg) per foot.

ROBERTS-GORDON

®

End Vent Plate for

End Burner Only

End Vent

Clips

Special Tube and Reflector Hanger

ROBERTS-GORDON

®

End Vent

Clips

CORAYVAC

®

Classic

Turnbuckle

Hang cast-iron combustion chamber with a turnbuckle

(spring clips will not fit around cast-iron hanging loop).

WARNING

Severe Injury Hazard

Hang heater with materials with a minimum
working load of 750 lbs. (340 kg).

Use special tube and reflector hangers when
suspending the schedule 40 steel pipe system.

Schedule 40 steel pipe is heavy and will fall if
not supported properly.

Distance between supports must be 7' (2.13 m)
or less.

Failure to follow these instructions can result
in death, injury or property damage.

Description

Part Number

Special Tube & Reflector Hanger

02790300

Turnbuckle

91903201

Cast-Iron Combustion Chamber

02721200-1P

Cast-Iron Adapter

02722100

Coupling

01312700

Advertising
This manual is related to the following products: