Caution, Correct positions, Incorrect positions (wrong installation) – Roberts Gorden CoRayVac CRV-B-6 User Manual

Page 50

Advertising
background image

CRV-S

ERIES

I

NSTALLATION

, O

PERATION

AND

S

ERVICE

M

ANUAL

44

FIGURE 27: Gas Connection with Flexible Gas Hose

Shut-Off Valve (included with gas hose) must
be parallel to burner gas inlet. The 3" (8 cm)
displacement shown is for the cold condition.
This displacement may reduce when the
system is fired.

CORRECT POSITIONS

Horizontal

45°

End View

Vertical

(as shown left)

Alternate
positions
okay

Flexible Gas Hose
36" (91 cm) length

3" (8 cm)
max. displacement

Side View

Heater Movement

12"

(30 cm)

CAUTION

Product Damage Hazard

Hold gas nipple securely with pipe wrench
when attaching gas hose.

Failure to follow these instructions can result
in product damage.

Description

Part Number

1/2" Flexible Stainless Steel Gas Hose (US Models)

91412200

3/4" Flexible Stainless Steel Gas Hose (US Models)

91412204

1/2" Rubber (Type 1) Gas Hose (Canadian Models)

91412206

3/4" Rubber (Type 1) Gas Hose (Canadian Models)

91412207

INCORRECT POSITIONS (WRONG INSTALLATION)

Heater Movement

Heater Movement

Heater Movement

Heater Movement

Advertising