5.2 General Technical Data Table (All Models)

Electrical load at 230 V 50 Hz measured by calculating from total run current of appliance.

* Do not exceed the maximum length of flue stated or heater may not operate properly.

Reduce the maximum length stated by 1 m for each 90° bend installed.

**If minimum air flow requirements are not met, then temperature limit devices will shut down the heater.

5.3 Technical Data Table (All Models)

Appliance Category II

2H/L 3B/P

Gas rates corrected to standard conditions 1013.25 mbar 15° C

Model

CTCU-7

CTCU-11

CTCU-15

CTCU-22

CTCU-27 / 32

CTCUA, Axial Fans

Total Electrical Load

W

260

274

336

384

345

Run Current

A

1.1

1.2

1.5

1.7

1.5

Start Current

A

1.7

1.8

2.5

2.9

2.6

Air Flow

m

3

/h

1120

1220

2710

2750

4474

Air Throw

m

9

12

14

16

16

Sound Pressure Level at 3 m

[NR]

dB(A)

[31]

37

[35]

41

[39]

45

[42]

48

[42]

48

Flue and AIr Intake

Flue and Air Intake Size

mm Ø

80

80

80

80

100

*Maximum Straight Flue/Air Intake

m

2.5

4

5

5

5

Model

CTCU-7

CTCU-11

CTCU-15

CTCU-22 CTCU-27

CTCU-32

Heat Input

Gross CV

kW

(Btu/h) x (1000)

8.5

29

13.4

46

18.3

62

27.5

94

33

113

38.5

131

Heat Input

Net CV

kW

(Btu/h) x (1000)

7.7

26

12.1

41

16.5

56

24.8

85

29.7

101

34.7

118

Approximate

Heat Output

kW

(Btu/h) x (1000)

7.1

24

11.1

38

15.1

52

23
78

27.2

93

31.7

108

Natural Gas (G20) Data - Inlet Pressure 20 mbar (7.8 in WG) Min. 17 mbar (6.8 in WG) Max. 25 mbar (10 in WG)

Burner Pressure

mbar

9.5

9.5

9.5

9.5

9.0

9.0

Gas Rate

m

3

/h

ft

3

/h

0.8

29

1.3

45

1.7

62

2.6

93

3.1

110

3.6

127

Natural Gas (G25) Data - Inlet Pressure 25 mbar (10 in WG) Min. 20 mbar (7.8 in WG) Max. 30 mbar (12 in WG)

Burner Pressure

mbar

9.0

9.0

9.5

9.2

9.2

9.3

Gas Rate

m

3

/h

ft

3

/h

0.9

33

1.5

52

2.0

72

3

108

3.6

127

4.2

148

LPG / Propane (G31) Data - Inlet Pressure 37 mbar (14.6 WG) Min. 25 mbar (10 in WG) Max. 45 mbar (18 in WG)

Alternative where permitted 50 mbar (20 in WG) Min. 42.5 bar (17 in WG) Max. 57.5 mbar (23 in WG)

Burner Pressure

mbar

25.6

29.4

29.4

28.6

29.9

29.9

Gas Rate

m

3

/h

kg/h

0.3

0.59

0.5

0.93

0.7

1.27

1

1.91

1.2

2.3

1.4

2.68

LPG / Butane (G30) Data - Inlet Pressure 29 mbar (11,4 in WG) Min. 20 mbar (7.8 in WG) Max. 35 mbar (13.8 WG)

Burner Pressure

mbar

19.2

21.9

22.9

21.4

21.4

22.4

Gas Rate

m

3

/h

kg/h

0.2
0.6

0.4

0.94

0.5

1.28

0.8

1.93

.9

2.31

1.1

2.7

Gas Connection

CTCUA

R - 1/2"

R - 1/2"

R - 1/2"

R - 1/2"

R - 1/2"

R - 1/2"