2 burner compartment – Roberts Gorden Compact Tubular Unit Heaters CTCU 27 User Manual

Page 43

Advertising
background image

SECTION 16: R

EMOVAL

AND

R

EPLACEMENT

P

ARTS

37 of 42

16.2 Burner Compartment

16.2.1 Burner Injectors

Remove flexible
air duct from spigot

Viewing port
for flame probe

Flame Probe

Burner
Compartment
Cover

Ignition Electrode

Remove screws and
pull off burner cover

The burner compartment is a sealed
compartment. Following any work,
re-seal the compartment with the gas
pipe rubber seal fully in place and all
screws fitted and tight.

MODEL

CTCU-7

CTCU-11

CTCU-15

CTCU-22

CTCU-27

CTCU-32

Injector Quantity

2

3

4

5

6

7

Natural Gas (G20)

Injector size mm Ø

1.78

1.85

1.85

2.06

2.057

2.057

in Ø

0.070

0.073

0.073

0.081

0.081

0.081

Marking

50

49

49

46

46

46

RG P/N

91930050

91930049

91930049

91930046

91930046

91930046

Natural Gas (G25)

Injector size mm Ø

1.99

2.06

2.06

2.26

2.261

2.261

in Ø

0.0785

0.081

0.081

0.089

0.089

0.089

Marking

47

46

46

43

43

43

RG P/N

91930047

91930046

91930046

91930043

91930043

91930043

LPG Propane (G31) and LPG Butane (G30)

Injector size mm Ø

1.18

1.18

1.18

1.25

1.25

1.25

in Ø

0.0465

0.0465

0.0465

0.049

0.049

0.049

Marking

56

56

56

1.25

1.25

1.25

RG P/N

91930056

91930056

91930056

91930125

91930125

91930125

Remove manifold

screws and pull

out manifold.

Manifold

Burners

Injectors

Manifold

Mounting

Bracket

Gromet

Unscrew

Injectors

Manifold

Marking

Ensure gas tight fitting of injectors.

Ensure correct alignment with burners.

Ensure all pipe joints are gas tight.

Advertising