Display modes, Table 2. display modes, Elapsed time mode – Omega Vehicle Security wall mount Multi-Channel DPS3300 User Manual

Page 8

Advertising
background image

Page 7


DISPLAY MODES


DPS3300 Series has multiple display modes and can be programmed to either scan, display the channel with the highest
reading, display the channel with the lowest reading, deviation between channel's process variable and a pre-programmed
setpoint, difference between any two selected channels or just run as a timer. In the timer mode the unit keeps track of
process run time with crystal controlled accuracy. Elapsed Time display format is 'HH.MM.SS' for hours, minutes, and
seconds. The desired display mode is selected during SYS SETUP ---- (for details refer to the SYS CONFIGURATION
section).

Table 2. Display Modes



MODE

FUNCTION PERFORMED


1) Elapsed time

Unit displays elapsed time since power up or last time reset.


2) Scan

All active channels are automatically scanned.

Channels that are turned off are not scanned or displayed.


3) High Channel

The unit will compare all active channels against each other and

display the one that has the highest process reading.



4) Low Channel

The unit will compare all active channels against each other and

display the one that has the lowest process reading.


5) Deviation

The unit scans all active channels and displays the deviation of

process variable from a pre-programmed setpoint.



6) Channel Differential The unit continuously displays the difference of process between

any two selected channels.




The following paragraphs give a detailed description and operation of various modes.

Elapsed Time Mode


DPS3300 Series can be programmed to run as timer. In this mode the unit will
indicate elapsed time in hours, minutes and seconds. The display format is
'HH.MM.SS'. This mode is selected during SYS Setup by opting for
'ELPSD t'. The elapsed time is the time passed since the unit was turned on or
when the time was last reset. To reset the time, first push the TIME key and
while keeping it pressed, push the RESET key. The display will show
'rESEt' and on release of the RESET key, the display will reset to '00.00.00'
and begin timing.

The elapsed time can also be momentarily displayed while the unit is
operating in any other display mode. This is done by pushing the TIME key
once. The unit will first display the word 'ELPSd t' followed by the elapsed time. This will stay in the display window for
a brief period and then the unit will revert to the normal display mode.

Advertising