SOFTWARE INSTALLATION

Copy the file ”F39-U1E_ver#.#.exe” and F39-U1E_ver#.#dat from

the 3.5--inch floppy disk (enclosed with the product) onto the hard

disk of the PC.

J

FUNCTION DESCRIPTION

Start Interlock

When the Start interlock function is used, the F3S-B does not go

to the ON-state automatically after power ON. Interrupting one or

more axes resets the start interlock condition of the F3S--B then

starts normal operation. The duration of the interruption must be

equal or shorter as defined in the »Max. interruption time (sec)« .

Max. Interruption Time

The max interruption time can be set between 0.3 and 2 s.

Note: In the case both the Start interlock and the Start/restart

interlock are selected, only the Start/restart interlock will

be activate.

Start/Restart interlock is a function which is selected by wiring.

Refer to the instruction manual of the F3S-B for more detailed

information.

Relay Monitoring

MPCEs (Machine Primary Control Elements) are usually relays

or contactors used to control hazardous movement directly. The

state of the MPCEs can be checked with the Relay monitoring

function.

A voltage of 17 VDC to Vs (Supplied voltage to F3S-B) has to be

applied to the Relay monitoring input through the NC contacts of

the MPCEs when the F3S-B control outputs are in the OFF--state

(see the F3S-B manual for wiring information). To ensure this

logic relation, the MPCEs must be safety approved types, with

forcibly guided contacts.

J

RATINGS AND PERFORMANCE

Allowed Relay Delay Time

The allowed relay delay time can be set between 20 and 300

ms. This delay time has to be set at least 20 milliseconds shorter

than the Outputs ON delay time.

Outputs ON Delay

You can set the ON delay time of control outputs between 80 and

400 ms. This corresponds to the time which the control outputs

go to ON-state after the detection zone is not interrupted.

Note: 1. When the Relay monitoring function is also used, the

ON delay time must meet the formula below.

2. ON delay time ≥ Allowed relay delay time + 20 ms

After the Relay monitoring function is set, if the ON

delay time does not meet the above formula, the
ON delay time will be changed automatically into

Allowed relay delay time + 20 ms.

Blanking

With the Blanking function, one or more axes can be disabled.

This function is useful in an application where a part of the F3S-B

detection zone is always interrupted. The Manual setting and the

Teaching setting are available to select the blanked axes.

Note: 1. In the case the blanked zone is not filled with structure

completely and remains some opening, the opening

must be filled with the protective structure.

2. All axes can not be disabled. At least one axis needs to

be active.

Type

F39-E1 Interface Unit

Supply voltage

24 VDC ± 20% (including 5 Vp--p ripple)

Current consumption

120 mA max.

Interface

RS-232C interface, RS--485 interface

Connection method

RS-485: 4pins, M 8 connector, RS--232C: D--SUB connector, 9 pins

Protection circuit

RS 485 protection against wrong wiring

Ambient temperature

During operation: -10 to 55° C (with no freezing), During storage: -25 to 70° C

Ambient humidity

During operation : 35 to 85% RH (with no condensation)

Ambient humidity

During storage: 35 to 95% RH

Insulation resistance

20 MΩ min. (at 500 VDC)

Dielectric strength voltage

500 VAC, 50/60 Hz, for 1 min.

Degree of protection

IEC60529, IP20

Shock resistance

Normal operation: 150 m/s

2

[15 G], ±X, ±Y and ±Z directions: 3 times

Vibration resistance

Normal operation: 10 to 55 Hz, double--amplitude: 0.3 mm, X, Y and Z directions: 10 sweeps

Cable length

RS-485 cable: 5 m (4 pin 0.25 mm

2

), RS--232C cable: Standard

Materials

Case: Aluminum

Size

122 x 60 x 35 mm

Conformity

EMC Directive