Mate screens, Page 49, Grid menu – Outback Power Systems Inverter/Charger VFX2612E User Manual
Page 49
 
Copyright 2003
OutBack Power Systems, Inc.
FX & VFX “E” Series Inverter/Charger System Installation & Programming Manual
19009 62
nd
Ave NE, Arlington WA 98223 USA
900-0027-2
Tel 360 435 6030 Fax 360 435 6019
Rev 7.1
06/08/06
Page 49
MATE SCREENS
GRID MENU
The GRID category of the advanced menu section allows for adjustment of the AC input voltage window and time delays to match the 
characteristics of the AC source if that AC source is the utility grid. This setting can be found in the SETUP/FX/INPUT menu. All 
OutBack Power System FX’s other than the “Grid-Tie” FX’s have a default of GEN (generator) as the AC source. If the AC source is 
the utility grid, return to the SETUP/FX/INPUT section (page 45) and change the ‘AC Transfer Control’ screen to GRID. 
ADV----------------- 
choose product: 
 
FX MATE 
↓
ADV/FX/PAGE1-------- 
choose category: 
 
ADV INV CHGR  PG2 
↓
ADV/FX/PAGE2-------- 
choose category: 
 
PG1 GRID GEN  PG3 
↓
ADV/FX/GRID------P00 
ac input 00.5 min 
connect delay 
DOWN INC DEC PORT 
↓
ADV/FX/GRID------P00 
ac1/grid 208 vac 
lower limit 
DOWN INC DEC PORT 
↓
ADV/FX/GRID------P00 
ac1/grid 270 vac 
upper limit 
DOWN INC DEC PORT 
↓
ADV/FX/GRID------P00 
ac1/grid 24.0 aac 
input limit 
DOWN INC DEC PORT 
↓
ADV/FX/GRID------P00 
ac1/grid 6 cycles 
transfer delay 
DOWN INC DEC PORT 
↓
ADV/FX/GRID--------- 
 GRID programming 
 completed 
 TOP ADV MAIN 
Once the password has been correctly entered, the ADV - CHOOSE PRODUCT is displayed. 
Selecting <FX> allows adjustment of the FX’s advanced programming. 
 
 
 
Selecting <PG2> advances the user to the second page of the advanced menu. 
 
 
 
 
Selecting <GRID> allows adjustment of the AC input set points and operation. 
 
 
 
 
The AC INPUT CONNECT DELAY set point adjusts the time period of when the FX sees an 
acceptable AC source to when it connects the AC loads to that source. This is useful to allow the 
utility grid to become stable after a utility power outage. This setting has a range between 0.2 
minutes to 15 minutes in 0.1 minute increments. 
 
The AC1/GRID LOWER LIMIT set point allows adjustment of the minimum voltage that the AC 
source is allowed to be in order for the FX to connect to that source. The FX will back off the 
charger if the AC source is at this lower limit. If the AC source falls below this limit, the FX will 
disconnect from the AC source until it is above this value. This setting has a range between 80 
vac and 220 vac in 2 vac increments. 
The AC1/GRID UPPER LIMIT set point allows adjustment of the maximum voltage that the AC 
source is allowed to be in order for the FX to connect to that source. If the AC source exceeds 
this value, the FX will disconnect from the AC source until it is below this value. This setting has a 
range between 250 vac and 300 vac in 2 vac increments. 
 
The AC1/GRID INPUT LIMIT sets the maximum amount of current the FX allows to be drawn 
from the AC source. When the AC input current limit is reached, the power draw of the battery 
charger is backed off to prevent overloading the AC source. If the AC loads exceed this limit, the 
FX will give a warning and start blinking the red “ERROR” LED. This setting has a range between 
2.5 aac and 30.0 aac in 0.5 aac increments. 
The AC1/GRID TRANSFER DELAY is the amount of time that the AC input will remain connected 
to the AC source when the AC input voltage drops below the AC1/GRID lower limit setting. 
Once the AC voltage has risen above the AC1/GRID lower limit setting for the AC INPUT 
CONNECT DELAY time period the AC source will be reconnected. This setting has a range 
between 0 cycles and 240 cycles in 1 cycle increments. 
Selecting TOP returns the user to the top of the ADV/FX/GRID menu section. Selecting ADV 
returns you to the advanced screen to allow selection of another product connected to the MATE. 
Selecting MAIN returns the display to the MAIN screen.