Mate screens, Page 51, Auxiliary menu – Outback Power Systems Inverter/Charger VFX2612E User Manual

Page 51

Advertising
background image

Copyright 2003

OutBack Power Systems, Inc.

FX & VFX “E” Series Inverter/Charger System Installation & Programming Manual

19009 62

nd

Ave NE, Arlington WA 98223 USA

900-0027-2

Tel 360 435 6030 Fax 360 435 6019

Rev 7.1

06/08/06

Page 51

MATE SCREENS

AUXILIARY MENU

The AUX (auxiliary) section can be used to control external AC or DC loads, signal a generator start system, send a fault alarm signal,
or to run a fan. The AUX output provides a 12 vdc, 0.7 adc output on the AUX terminals located in the AC wiring compartment.

ADV/FX/PAGE1--------
choose category:

ADV INV CHGR PG2

ADV/FX/PAGE2--------
choose category:

PG1 GRID GEN PG3

ADV/FX/PAGE3--------
choose category:

PG2 AUX STACK PG4

ADV/FX/AUX-------P00
aux output AUTO
control
DOWN INC DEC PORT

ADV/FX/AUX-------P00
aux output AC Drop
function
DOWN INC DEC PORT

ADV/FX/AUX-------P00
aux output DivertAC
function
DOWN INC DEC PORT

ADV/FX/AUX-------P00
aux output DivertDC
function
DOWN INC DEC PORT

ADV/FX/AUX-------P00
aux output Cool Fan
function
DOWN INC DEC PORT

ADV/FX/AUX-------P00
aux output Vent Fan
function
DOWN INC DEC PORT

ADV/FX/AUX-------P00
aux output Fault
function
DOWN INC DEC PORT

ADV/FX/AUX-------P00
aux output GenAlert
function
DOWN INC DEC PORT

ADV/FX/AUX-------P00
aux output LoadShed
function
DOWN INC DEC PORT

ADV/FX/AUX-------P00
aux output Remote
function
DOWN INC DEC PORT

Once the password has been correctly entered, the ADV - CHOOSE CATEGORY: screen is

displayed. Selecting <PG2> shows a second screen of categories.


Selecting <PG3> shows a third screen of categories.


Selecting <AUX> allows adjustment of the auxiliary output set points and operation. The AUX

OUTPUT CONTROL

screen allows selection of the mode of the AUX output. Selecting INC or

DEC changes the mode between OFF, AUTO, and ON. Selecting OFF disables the AUX output

from operating. Selecting AUTO allows the AUX output to automatically perform the function that

is selected in the AUX OUTPUT FUNCTION screens below. Selecting ON forces the AUX

output to be kept ON regardless of the function selected. Pressing <DOWN> allows the selection

of the AUX OUTPUT FUNCTION. There are nine functions in this section. The default setting is

“Cool Fan” which is set to run a Turbo Kit without any programming. The function at the top of

the menu is “AC Drop”. The user must press <INC> three times in order to get to the top of the

list of functions.

Selecting AC DROP enables the AUX output when an AC source is connected to the FX. When

the AC source ceases (due to a power outage, or a generator quitting) the Aux output will be

deactivated. This allows the user to attach an indicator to the AUX output to show the user when

an AC source is connected.

Selecting DIVERT enables the AUX output to function as a diversion controller. This can be

used to send excess power from a renewable energy source to a load. This can allow control of

sources such as wind turbines or hydro-generators. Two choices of DIVERT are provided –

‘DivertDC’ and ‘DivertAC’. ‘DivertDC’ is used to divert power to DC loads and ‘DivertAC’ is used

to divert power to AC loads. The only difference is that the ‘DivertAC’ setting will turn off the AUX

output if the inverter is overloaded. See the next page to adjust the set points for this function.

Selecting COOLFAN (default) enables the AUX output to function as a thermostatically operated

ventilation system controller. When the FX approaches an over temperature condition, the AUX

output will be energized. This can be used to power a small 12 vdc brushless “muffin” type fan,

the Turbo Kit, or can be used to control a larger cooling fan via a 12 vdc coil relay.
Selecting VENTFAN enables the AUX output to function as an automatic battery ventilation

system controller. The AUX output can provide 0.7 amps of power for connection to a 12 vdc

brushless “muffin” type fan. The fan will be automatically turned on when the voltage exceeds

the VENTFAN ON voltage set point. The fan can be set to operate intermittently by adjusting the

VENTFAN OFF TIME PERIOD. See the next page to adjust the set points for this function.
Selecting FAULT enables the AUX output to function as an alarm output. When the FX enters

any of the error conditions, the AUX output is energized. This can be used to send an alarm

signal via radio, pager or telephone dialer. It also can be used to log error conditions by using it

to trigger an event recording device.

Selecting GENALERT enables the AUX output to function as a simple voltage controlled

generator start signal. ‘GenAlert’ can be used to “alert” the system user to start the generator

due to the battery voltage being low. Only connection to a 2-wire type generator is possible and

must be done through a 12 volt DC relay. Time delays for ON and OFF are adjustable. Using

‘Advanced Generator Start’ (AGS) will override any AUX function that is programmed. See the

next page to adjust the set points for this function.
Selecting LOADSHED enables the AUX output to function as a load management system. When

the battery voltage drops below the LOAD DISCONNECT set point for more than 3 seconds, the

AUX output is energized. Connecting a normally closed (NC) relay to the circuitry of non-vital

loads will disengage them with this function. LOADSHED will also occur when the FX

approaches an over-temperature condition or when the AC output voltage drops below 202 vac

for more than 3 seconds. There is a 3-minute fixed delay before the AUX output is de-energized.

See the next page to adjust the set points for this function.

Selecting REMOTE enables the AUX output to be controlled by the MATE or a PC computer

connected to the MATE PC communication port. This function is currently not operational. It will

be operational in the future.

Press <DOWN> after selecting the AUX OUTPUT FUNCTION of your choice. The AUX menu

section is continued on the following page.

Advertising
This manual is related to the following products: