2 wiring – Toshiba Tosvert Inverter E6580772 User Manual

Page 10

Advertising
background image

E6580772

9

2.2 Wiring

When conduct wiring, follow the instructions below.

•

Use shield wire for control signal line and ground the unit with shield wire.

•

Applicable wire size for TB1 is 0.2 to 2.5mm

2

.

For TB2, it is 0.2 to 1.5mm

2

.

•

Peel off the end of the wire by about 5mm (7mm for TB1).

•

For connecting wires, use screwdriver that has a blade tip of 0.4mm thickness and 2.5mm width.

(For TB3, thickness and width should be 0.6mm and 3.5mm.)

•

Tightening torque of the terminal block should be 0.22 to 0.25N

・

m .

(For TB1, it is 0.5 to 0.6N

・

m.)

•

Never bind the signal line and main circuit connection wire together.

Separate the signal line and the main circuit connection wire by more than 200mm.

•

Use 0.75mm

2

wire for the connection of PGCC terminal of the option side and CC terminal of the inverter.

•

Use 0.75mm

2

wire for the connection of grounding terminal of the option side and that of the inverter.

„

< PG interface > [ TB2 terminal]

Terminal

name

Function

Specification

Internal circuit

PGA1

PGA2

PG feedback input,
Pulse row speed
command input
(Phase A input)

PGB1

PGB2

PG feedback input
Pulse row speed
command input
(Phase B input)

PGZ1

PGZ2

PG feedback input
Pulse row speed
command input
(Phase Z input)

PG feedback

•

15V complementary / open
collector

•

12V complementary / open
collector

•

Maximum input frequency

60kpps (2 phases)
120kpps (single phase)

•

Pulse duty

50 ± 10%

Photocoupler
V

F

:1.2~1.7V

PGVC

PGCC

PG power supply terminal 12VDC

160mA or less