3.2.4 Vector control setting parameter

During operation with vector control with sensor, it is necessary to set the following parameters shown in the
table below.

<Basic parameters>

Title

Function

Name

Parameter Setting

Setting at
Shipment

0

pt

Motor control
mode
selection

0: Constant torque
1: Variable torque mode
2: Automatic torque boost
3: Sensorless vector control (speed)
4: Automatic torque boost + automatic energy-saving
5: Sensorless vector control (speed) + automatic energy-saving
6: V/F 5-points setting
7: Sensorless vector control (speed/torque switching)
8: PG feedback vector control (speed/torque switching)
9: PG feedback vector control (speed/position switching)

Standard :
speed control

When conducting vector control with sensor (speed/torque control) with this F10M option unit is added, pt=8
should be set.
For torque control operation, it is necessary to allocate control switching (torque/position) to one of the terminal
function selection f110 to f118 (input terminal selection 1 to 8) (cmod =0) or to set operation
switching by communication system (cmod = 2 to 4) in addition to the above parameters.
For details of adjustment methods by the speed control command and torque control command, refer to the
inverter’s instruction manual.

Extended Parameter

Title

Function Name

Parameter Setting

Setting at Shipment

f367

Number of PG input pulse

1~9999

500

f368

Selection of number of PG input phases 1: Single phase input

2: 2-phase input

2

f374

Current control proportional gain

0.1~1000

Depends on type.

f375

Current control integral gain

0.1~1000

Depends on type.

f376

Speed loop proportional gain

3.2~3270

Depends on type.

f377

Speed loop integral gain

0.8~125.0(rad/sec)

Depends on type.

f400

Auto tuning

0: No auto tuning (internal table)
1: Motor constant initialization
2: Auto tuning (0 after execution)

0

f401

Slip frequency gain

0.00~2.55

0.60

f402

Motor constant 1

(primary resistance)

0.01~100000mΩ

Depends on type.

f403

Motor constant 2

(secondary resistance)

0.01~100000mΩ

Depends on type.

f404

Motor constant 3

(exciting inductance)

0.1~6500mH

Depends on type.

f405

Motor constant 4

(load inertia moment)

0.1~100.0

1.0

f410

Motor constant 5

(leak inductance)

0.01~650.0mH

Depends on type.

f411

Number of poles of motor

2, 4, 6, 8, 10, 12, 14, 16

4

f412

Rated capacity of motor

0.1~280kW

Depends on type.

f413

Motor type

0: TOSHIBA Standard Motor 1
1: TOSHIBA VF motor
2: TOSHIBA V3 motor
3: TOSHIBA Standard motor 2
4: Other

0

The motor constant parameter (f400 to f413) requires setting according to the motor used.
For details, refer to the inverter manual.