Operator interface – Trane CVHE-SVU01E-ENX39640712050 User Manual

Page 43

Advertising
background image

43

CVHE-SVU01E-EN

Operator
Interface

Display Settings
Description

Units

notes

1. Date Format

(“mmm dd, yyy”, “dd-mmm-yyyy”), “mmm dd, yyy”

2. Date

4

3. Time Format

(12-hour, 24-hour), 12-hour

4. Time of Day

4

5. Keypad and Display Lockout

(Enable, Disable), Disable

5

6. Display Units

(SI, English), English

7. Language

(English, Selection 2, Selection 3), English

6

(1) Temperatures will be adjustable to 0.1 degree F or C. The Main Processor provides the minimum and maximum allowable value.
(2) Adjustable to the nearest whole number percent. The Main Processor provides the minimum and maximum allowable value.
(3) Terminates with 10 minutes if inactivity
(4) The Date and Time setup screen formats deviate slightly from the standard screens defined above. See the time and date section for further details.
(5) Enables a DynaView

Lockout screen. All other screens timeout in 30 minutes to this screen when enabled. The DynaView

Lockout Screen displays a 0-9 keypad to

permit the user to exit the lockout with a fixed password (1-5-9 + Enter). See lockout setion for further details.

(6) Language choices are dependent on what has been setup in the Main Processor. Language selections will include English and qty 2 alternate as loaded by TechView

.

Language shall always be the last setting listed on the Display Settings menu. This will allow a user to find language selection if looking at an unrecognizable language.

(7) Manual Compressor Control allows an operator to override the Auto Control and manually control the compressor while in operation. This is not active during Stop

mode.

Purge
Description

Units

Default

1. Purge Operating Mode

(Auto, On, Adaptive, Stop), Adaptive

2. Daily Pumpout Limit

Minutes

3. Disable Daily Pumpout Limit

Hours

4. Purge Liquid Temperature Inhibit

(Enable, Disable),

Enable

5. Purge Liquid Temperature Limit

Temperature