Control system components – Trane CVHE-SVU01E-ENX39640712050 User Manual

Page 58

Advertising
background image

CVHE-SVU01E-EN

58

Control System
Components

GBAS (Generic Building Automation System)
1A15 Optional Dual

GBAS

Signal #1

Percent RLA Compressor Output

J2-1 Output #1, J2-3 Ground

Analog Input/

or

output Module

CDRP

1A16 Optional Dual

GBAS

Signal #1

External Current limit Setpoint

J2-2 Input #1, J2-3 Ground

Analog Input/
output Module
1A16 Optional Dual

GBAS

Signal #2

Chilled Water Reset input,

J2-5 Input #2, J2-6 Ground

Analog Input/

or External Chiller Water Setpoint

output Module

Percent RLA Output
2 to 10 Vdc corresponding to 0 to
120% RLA. With a resolution of
0.146%. The Percent RLA Output
connections are on the terminals
1A15 –J2-1 (+) to J2-3 (Ground). The
Percent RLA Output is polarity
sensitive.

The following graph illustrates the
output:

Figure 23. Voltage versus percent RLA

Notes: 0% RLA = 2 vdc

120% RLA = 10 vdc

Example: If RLA is 500 amps then
10 vdc = 600 amps.