G8000 Series Installation and operation Manual

11.6 Control Wires

The control wires terminal layouts at Tb1 (terminal bus 1) are shown below in Table 11.8.

TABLE 11.8 EXTERNAL CONNECTIONS

no.

I/o

Signal name

operation

1

output

low battery

Closed at low battery

2

output

backup operation

Closed during backup operation

3

output

Fault

Closed if Faults present

4

output

Inverter Supply

Closed during normal operation

5

output

warning

Closed if warnings present

6

Input

p24

7

Input

remote run

Close to run UpS

8

Input

p24

9

Input

remote Stop

Close to stop UpS

10

output

bypass Supply

Close during bypass operation

11

output

output Signal Ground

(Ground for pin #1 – 5 & #10)

12

Input

p24

battery’s

13

Input

battery overheat

overheat b-contact

14

output

bypass breaker

15

output

52C Trip Signal

Shunt Trip Signal by epo

16

output

battery breaker shunt trip

17

output

72b Trip Signal

by epo or battery shutdown

18

output

battery breaker’s

19

output

72b Aux. Contact

Auxiliary A-contact

20
21

output

external epo

ext epo (Customer) n.o. Contacts

22

output

external epo

ext epo (Customer) n.o. Contacts

note: All control wiring should be #18 AwG (0.823 mm

2

) or larger.

}

}

}

}

}

}
}