7 grounding configuration – Toshiba G8000 User Manual

Page 48

Advertising
background image

40

G8000 Series Installation and operation Manual

11.7 Grounding Configuration

This section describes the grounding configuration to be used with various AC service entrance configurations.
Inadequate grounding will cause problems at start-up. Connections for the ground line and the neutral

line must be made appropriately according to the system configuration.

11.7.1 Recommended configuration (for 4 wire input with Input Neutral

grounded)

Figure 11.12 shows recommended grounding configuration when the input neutral is grounded.
The neutral line at the input source is usually grounded. The neutral terminal in the UpS cabinet should

be disconnected from the ground bus. The neutral connection for the UpS bypass input should be

grounded.

FIGURE 11.12 - GROUNDING CONFIGURATION WITH INPUT NEUTRAL GROUNDED

A 2 AwG (or 38 mm

2

) jumper cable is provided between the neutral terminal and ground bus in the UpS

cabinet. The qualified personnel should remove the jumper cable in this configuration. The jumper cable

location is illustrated below.

FIGURE 11.13 - JUMPER CABLE BETWEEN THE NEUTRAL TERMINAL & GROUND BUS

n

G

3

Ǿ

3

Ǿ

3

Ǿ

n

G

< UpS Cabinet >

n

3

Ǿ

3

Ǿ

G

Input Source

remove

Jumper Cable

G

n

3

Ǿ

To the

load

n

G

3

Ǿ

3

Ǿ

3

Ǿ

n

G

< UpS Cabinet >

n

3

Ǿ

3

Ǿ

G

Input Source

Jumper Cable

remains in place

G

n

3

Ǿ

To the

load

n

G

3

Ǿ

3

Ǿ

3

Ǿ

n

G

< UpS Cabinet >

3

Ǿ

3

Ǿ

G

Input Source

Jumper Cable

remains in place

G

n

3

Ǿ

To the

load

n

G

3

Ǿ

3

Ǿ

3

Ǿ

n

G

< UpS Cabinet >

G

n

3

Ǿ

3

Ǿ

To the

load

output Distribution

3

Ǿ

3

Ǿ

G

Input Source

b

Ǿ

remove

Jumper Cable

Ground

bus

remove

Jumper

Cable

neutral

Terminal

Ground

bus

remove

Jumper

Cable

300 kVA

100-225 kVA

neutral

Terminal