The alarm relay card, Overview, Mounting – Tyco 4100U User Manual

Page 107: The alarm relay card -7, Overview -7, Mounting -7, Figure 6-1

Advertising
background image

6-7


The Alarm Relay Card mounts on, and is driven by, the SPS. It has 3 relays each
providing one set of voltage-free contacts.

The relays are able to be configured under custom control, but the default operation is for
system status, i.e. Fault (Trouble), Isolate (Supervisory), and Alarm, respectively. These
are commonly used to drive the Brigade signalling.

TROUBLE

SUPERVISORY

ALARM

F3

F2

F1

p
3

p
2

p
1

LD1

LD2

LD3

Fault

(Trouble)

Isolate

(Supervisory)

Alarm

10 Way FRC

connects to P7

on SPS

Energised Relay LEDs

Energised Relay LEDs

Normally Closed/
Normally Open
Jumpers

3A, 5 x 15mm Fuses

TB1 Terminal Block

Figure 6-1. The Alarm Relay Card

The Alarm Relay Card mounts on the SPS adjacent to the largest relay K3. With the
power disconnected, fit the card using the 3 plastic stand-offs and one Torx screw with
plastic sleeve.

Connect P4 on the relay card to P7 on the SPS with the 10 way FRC provided.


The Alarm Relay Card