Tic/motherboard interconnections (4100u), Tic/motherboard interconnections (4100u) -10, Figure 4-3 – Tyco 4100U User Manual

Page 78: Transponder cabinet interconnections -10, Ti sps or rps c pdi 1 pdi 2

Advertising
background image

4-10

4100 POWER DISTRIBUTION INTERFACE

ASSY 566-084

4100 POWER DISTRIBUTION INTERFACE

ASSY 566-084

LED4

SW1

LED1

TB2

PRI

LED2

P1

P3

LED5

TB3

SEC

RUI

TMPR SW

24C INPUT

SHLD

4100

COMM

LOSS

RUI
G.F.

SEARCH

AUDIO RISER CARD

HARNESS
734-008

TI

SPS

OR

RPS

C

PDI 1

PDI 2

HARNESS

734-078

P1

P6

POWER/
COMM

Connectors with

White Wire go to P3

HARNESS 733-525

Connectors with
Blue Wire go to P2


Use Figure 4-3 to connect the TIC to a motherboard in another bay.

















































Figure 4-3. Transponder Cabinet Interconnections

TIC/Motherboard Interconnections (4100U)

PDI Jumpers
P4 and P5 on the PDI must be configured to provide power to the TIC.
--- If there is a Power Supply in Bay 1,

• Set Jumpers P4 and P5 in Bay 1 to Positions 2 and 3.

--- If there is no Power Supply in Bay 1 with the TIC, you must obtain

power from Bay 2 or Bay 3.
Option 1

• Set Jumpers P4 and P5 in Bay 1 to Positions 1 and 2.
• Connect one end of Harness 734-008 to Power/Comm

plug on the SPS or RPS (P6) (or P2 on XPS) located in
Bay 2 or Bay 3. Connect the other end of the harness to
P1 in Bay 1.

Option 2

• Set Jumpers P4 and P5 in Bay 1 to Positions 1 and 2.
• Set Jumpers P4 and P5 to Positions 2 and 3 in bay with

power supply that will provide power to the TIC in Bay 1.

• Connect one end of Harness 734-008 to P2 or P3 in bay

that will provide power to the TIC in Bay 1. Connect the
other end of the harness to P1 in Bay 1.