Example Table Excerpt:

Register

Function / Title

Bank

Mask

Adjustment Range

Multiplier

26

MAXIMUM OUTPUT

FREQUENCY

(

∗∗∗∗

)

0 / 1

FFFF

0BB8

9C40 (30.00

400.00)

0.01

27

BASE FREQUENCY #1

0 / 1

FFFF

09C4

9C40 (25.00

400.00)

0.01

28

BASE FREQUENCY

VOLTAGE SELECT

(

∗∗∗∗

)

0 / 1

0030

0000: Input voltage level

(0)

0020: Automatic setting

(1)

0030: Stationary setting

(2)

29

MAXIMUM OUTPUT
VOLTAGE #1

0 / 1

FFFF

0000

0258 (0

600)

1

2A

REVERSE OPERATION
DISABLE SELECT

0 / 1

0020

0000: Reverse allowed

(0)

0020: Reverse not allowed

(1)




Other Programming Register Notes:

= All register numbers indicated are in hexadecimal notation (for example, 29 hex =

41 decimal). Occasionally, hexadecimal notation in this document may also take
the form of a number beginning with “0x”.

= Throughout this document, the abbreviations "LL", "UL", and "Fmax" will stand for

LOWER LIMIT FREQUENCY

,

UPPER LIMIT FREQUENCY

, and

MAXIMUM

OUTPUT FREQUENCY

, respectively.

= Reading from or writing to registers marked as "Reserved" will generate an

“invalid register” error (error code 0x0003)

= Certain parameter registers cannot be written to while the inverter is running.

These registers will be indicated by the character (

∗∗∗∗

). If an attempt is made to

write to these registers while the inverter is running, a “cannot execute” error
(error code 0x0001) will be generated.

= The parameter register data for all read/write registers with Bank information

listed as 0/1 will be retrieved from bank 0 (RAM) during reads and will be written
to both banks 0 and 1 (RAM and EEPROM) during writes.

= All parameters in

GROUP:COMMUNICATION SETTING PARAMETERS

(section

11.2.10) are retrieved by the drive from non-volatile memory upon inverter
initialization only. When any of these registers are modified, therefore, the drive
must be reset for the changed values to take effect.

= If the

COMMAND MODE SELECTION

or

FREQUENCY MODE SELECTION

parameters are changed while the drive is running, the change will not take effect
until the next time the drive is stopped.