Table 5: inverter status 1 (register 0e), Table 6 : inverter status 2 (register 0f) – Toshiba G3 TOSVERT-130 User Manual

Page 33

Advertising
background image

32

(Note 3)

If the input / output power units data is 0, the monitored data is in 0.01kW units, and the multiplier is
0.01. If the input / output power units data is 1, the monitored data is in 0.1kW units, and the multiplier
is 0.1. These values are automatically set according to the inverter’s capacity.


Table 4: Output Terminal Status Monitor (register 0D)

Lower

Byte

Bit Output

Terminal

0

1

Single-Bit

Read Mask

bit 0

unused (always 0)

bit 1

unused (always 0)

bit

2

FAN

OFF

ON

0004

bit 3

FL

FLB-FLC shorted

FLA-FLC shorted

0008

bit 4

MS relay

OFF

ON

0010

bit 5

OUT (option)

OUTB-OUTC shorted

OUTA-OUTC shorted

0020

bit 6

RCH

RCHA-RCHC open

RCHA-RCHC shorted

0040

bit 7

LOW

LOWA-LOWC open

LOWA-LOWC shorted

0080

Table 5: Inverter Status 1 (register 0E)

Lower

Byte

Bit Inverter

Status

0

1

Single-Bit

Read Mask

bit 0

running (acc/dec)

running 0001

bit 1

unused (always 0)

bit 2

forward / reverse

reverse

forward

0004

bit 3

acc/dec #1/#2

acc/dec #1

acc/dec #2

0008

bit 4

for inverter use

bit 5

for inverter use

bit 6

for inverter use

bit 7

jog/normal mode

normal (acc/dec)

jog mode

0080

Upper

Byte

Bit Inverter

Status

0

1

Single-Bit

Read Mask

bit 0

feedback ON/OFF

OFF

feedback active

0001

bit 1

DC inj. braking

OFF

DC inj. braking active

0002

bit 2

V/F #1/#2

V/F #1

V/F #2

0004

bit

3

coasting not

coasting coasting

0008

bit 4

emergency off

not in emergency off

in emergency off

0010

bit 5

for inverter use

bit 6

for inverter use

bit 7

for inverter use

Table 6 : Inverter Status 2 (register 0F)

Upper

Byte

Bit Inverter

Status

0

1

Single-Bit

Read Mask

bit

0

accelerating not

accelerating accelerating 0001

bit

1

decelerating not

decelerating decelerating 0002

bit 2

for inverter use

bit

3

retry

not

retrying

retrying

0008

bit 4

running (including DC

injection braking)

stopped running

0010

bit 5

for inverter use

bit 6

for inverter use

bit

7

tripped not

tripped tripped

0080