High Efficiency Propeller Fan Gas Unit Heater •

GHND-SVX01A-EN

Operation

Notes:

This schedule is for units operating at normal altitudes of 2000 ft. (610m) or less. SPECIAL ORIFICES ARE

REQUIRED FOR INSTALLATIONS ABOVE 2,000 FT. (610M).

Notes:

When installed in Canada, any references to deration at altitudes in excess of 2000 feet (610m) are to be

ignored. At altitudes of 2000 to 4500 feet (610 to 1372m), the unit heaters must be orificed to 90% of

the normal altitude rating, and be so marked in accordance with the CSA certification.

Table 6.

Main burner orifice schedule

Input in 1000 BTU

Type of Gas

Natural

Propane

Number of
Burner
Orifices

Heating Value

1075 BTU/Ft3
(40.1 MJ/m3)

2500 BTU/Ft3
(93.1 MJ/m3)

Manifold Pressure

3.5" W.C.
(0.87kPA)

10" W.C.
(2.49 kPA)

30

FT 3/HR
ORIFICE DRILL

28
49

12
57

2

45

FT 3/HR
ORIFICE DRILL

42
49

16
57

3

60

FT 3/HR
ORIFICE DRILL

56
49

24
57

4

75

FT 3/HR
ORIFICE DRILL

70
49

30
57

5

100

FT 3/HR
ORIFICE DRILL

96
42

40
54

4

125

FT 3/HR
ORIFICE DRILL

120
42

50
54

5

150

FT 3/HR
ORIFICE DRILL

140
42

60
54

6

175

FT 3/HR
ORIFICE DRILL

163
42

70
54

7

200

FT 3/HR
ORIFICE DRILL

186
42

80
54

8

225

FT 3/HR
ORIFICE DRILL

210
42

90
54

9

250

FT 3/HR
ORIFICE DRILL

233
42

100
54

10

300

FT 3/HR
ORIFICE DRILL

280
42

120
54

12

350

FT 3/HR
ORIFICE DRILL

326
42

140
54

14

400

FT 3/HR
ORIFICE DRILL

372
42

160
54

16