Z. hi-limit switch tripping, Aa. noisy power venter, Bb. power venter will not run – Trane GHND-SVX01A-EN User Manual

Page 45: Trouble shooting

Advertising
background image

GHND-SVX01A-EN • High Efficiency Propeller Fan Gas Unit Heater

45

Trouble Shooting

If present, replace main valve; if not,replace S8600 Igniter.

Z. Hi-Limit switch tripping.

POSSIBLE CAUSE(S)

1.

Vertical run of flue is too short.

2.

Unit is overfiring.

3.

Air flow too low

CORRECTIVE ACTION

Lengthen vertical run of flue pipe (see venting).

Burner orifice may be too large:verify/replace if required.

Increase air flow; check fan size.Check for proper voltage.

Replace.

AA. Noisy power venter.

POSSIBLE CAUSE(S)

1.

Power venter wheel loose.

2.

Power venter wheel dirty.

3.

Power venter wheel rubbing housing.

4.

Bearings are dry.

CORRECTIVE ACTION

Replace or tighten.

Clean power venter wheel.

Realign power venter wheel.

Oil bearings on power venter motor. (Refer to label on motor).

BB. Power venter will not run.

POSSIBLE CAUSE(S)

1.

Loose wiring.

2.

Defective motor overload protector or defective motor.

3.

Defective power venter relay.

CORRECTIVE ACTION

Check and tighten all wiring connections per diagrams. Thermostat wires tagged
"W" and "G" must be connected together (unless special thermostats are used; if so,
see thermostat wiring diagram). See electrical connections.

Replace motor.