Toshiba, Group:special control parameters – Toshiba Adjustable Speed Drive H3 User Manual

Page 39

Advertising
background image

TOSHIBA

8 - 4

GROUP:SPECIAL CONTROL PARAMETERS

PARAMETER

DESCRIPTION

LIQUID CRYSTAL DISPLAY

ADJUSTMENT

RANGE

ITEM

NO.

PAGE

NO.

DISPLAY

RESOLUTION

FACTORY

SETTING

START-UP FREQUENCY

31

Start-up frequency

0.0 - 10

0.1/0.01 Hz

0.1

9-6

END FREQUENCY

32

End frequency

0.0 - 30

0.1/0.01 Hz

0.1

9-6

RUN FREQUENCY

33

Run frequency

0.0 - max output freq

0.1/0.01 Hz

0.0

9-6

RUN FREQUENCY

34

Run frequency hysteresis

0.0 - 30

0.1/0.01 Hz

0.0

9-6

HYSTERESIS

ENABLE JUMP

35

Jump frequency enable

0: Function OFF

-

0

9-6

FREQUENCIES

1: Function ON *

JUMP FREQUENCY #1

36*

Jump frequency #1

0.0-Max Output Freq

0.1/0.01 Hz

0.0

9-6

JUMP FREQUENCY #1

37*

+/- band # 1

0 - 30

0.1/0.01 Hz

0.0

9-7

BANDWIDTH

JUMP FREQUENCY #2

38*

Jump frequency #2

0.0-Max Output Freq

0.1/0.01 Hz

0.0

9-7

JUMP FREQUENCY #2

39*

+/- band # 2

0 - 30

0.1/0.01 Hz

0.0

9-7

BANDWIDTH

JUMP FREQUENCY #3

40*

Jump frequency #3

0.0-Max Output Freq

0.1/0.01 Hz

0.0

9-7

JUMP FREQUENCY #3

41*

+/- band # 3

0 - 30

0.1/0.01 Hz

0.0

9-7

BANDWIDTH

PWM CARRIER

42

PWM carrier frequency for 230V

500 Hz - 10 kHz

0.1kHz

2.2 kHz

9-7

FREQUENCY

(.75-30 HP)

PWM carrier frequency for 460V

500 Hz - 10 kHz

(1-125 HP)

PWM carrier frequency for 460V

500 Hz - 5 kHz

(125-300 HP)

*Items 36 - 41 are available only when Item 35 Adjustment Range option 1 is selected.

Specifications

Precautions

Wiring

Jumpers

Panel

Keypad

Parameters

Programming

Service

Dimensions

Index

Inspection

Advertising