17

Change of lighting time of filter sign

According to the installation condition, the lighting time
of the filter sign (Notification of filter cleaning) can be
changed.

Follow to the basic operation procedure

(

1

2

3

4

5

6

).

• For the item code in Procedure

3

, specify [01].

• For the [Set data] in Procedure

4

, select the setup

data of filter sign lighting time from the following
table.

Setup data

0000

0001

0002

0003

0004

Filter sign lighting time

None

150H (At shipment from factory)

2500H

5000H

10000H

To secure better effect of heating

When it is difficult to obtain satisfactory heating due to
installation place of the indoor unit or structure of the
room, the detection temperature of heating can be
raised. Also use a circulator, etc. to circulate heat air
near the ceiling.

Follow to the basic operation procedure

(

1

2

3

4

5

6

).

• For the item code in Procedure

3

, specify [06].

• For the set data in Procedure

4

, select the setup

data of shift value of detection temperature to be set
up from the table below.

Setup data

0000

0001

0002

0003

0004

0005

0006

Detection temp shift value

No shift

+1°C

+2°C (At shipment from factory)

+3°C

+4°C

+5°C

+6°C

Adjustment of air direction

1. Using the remote controller switch, change the up/

down air direction by moving the horizontal flap.

2. Adjust the right/left air direction by bending the

vertical grille inside of the air outlet port with hands.

REQUIREMENT

Do not touch the horizontal flap directly with
hands; otherwise a trouble may be caused.

For handling of the horizontal flap, refer to
“Owner’s Manual” attached to the outdoor unit.

Group control

In a group control, a remote controller can control up
to maximum 8 units.

• The wired remote controller only can control a group

control. The wireless remote controller is unavailable
for this control.

• For cabling procedure and cables of the individual

line (Identical refrigerant line) system, refer to
“Electric work” in this Manual.

• Cabling between indoor units in a group is performed

in the following procedure.

Connect the indoor units by connecting the remote
controller inter-unit cables from the remote controller
terminal blocks (A, B) of the indoor unit connected
with a remote controller to the remote controller
terminal blocks (A, B) of the other indoor unit.
(No polarity)

• For address setup, refer to the Installation Manual

attached to the outdoor unit.

NOTE

Net work adapter (Model TCB-PCNT20E) can not
connect to this High Wall type air conditioner.

10

APPLICABLE CONTROLS