2

To the Installer

Models 382/RC25

Refrigeration Charging and Line

Construction

The dispensing unit is shipped with a refrigerant

holding charge that is sufficient enough to prevent

moisture contamination (8 oz./227 g. HP62). This

holding charge will become part of the total system

charge.

The condensing unit is shipped with the total amount

of refrigerant required for a typical installation of 75 ft.

or less with a single dispenser. For other installation

configurations, use the following chart for line sizing

and for adding required refrigerant.

Recommended System Refrigerant

Charge

Domestic

Suction Line

Length

Dispenser Required Charge

Less than 75 ft.

Single

10 lb.

More than 75 ft.

Single

12 lb. (add 2 lb.)

Less than 75 ft.

Dual

13 lb. (add 3 lb.)

More than 75 ft.

Dual

15 lb. (add 5 lb.)

International

Suction Line

Length

Dispenser Required Charge

Less than 22.8 m

Single

4.5 kg

More than 22.8 m

Single

5.4 kg (add 0.91 kg)

Less than 22.8 m

Dual

5.9 kg (add 1.4 kg)

More than 22.8 m

Dual

6.8 kg (add 2.3 kg)

Note: Maximum line length is 150 ft. (45.7 m).

Note: To meet individual installation requirements,

lines must be purchased and constructed locally.

Line Size

Liquid Line - Single or dual dispensers require 3/8”

refrigerant grade copper tubing (hard or soft).
Note: Insulating the liquid line is recommended if it is

exposed to high ambient conditions. This will reduce

heat accumulation and prevent the formation of flash

gas in the liquid line.

Single Dispensing Installations

Suction Line - Less than 75 ft. (22.8 m) total line

length requires 5/8” refrigerant grade copper tubing

(hard or soft). Maximum 5/8” tubing length is 75 ft.

(22.8 m).

Note: Suction lines must be insulated.

Suction Line - More than 75 ft. (22.8 m) total line

length requires 3/4” refrigerant grade copper tubing

(hard or soft). Maximum tubing length is 150 ft. (45.7

m).

Dual Dispensing Installations

(One Condenser, Two Dispensers)

Individual Suction Line - Requires 5/8” refrigeration

grade copper tubing (hard or soft) from each dispenser

to the common suction tube.

Common Suction Line - Requires 3/4” refrigeration

grade copper tubing.

Note: Lines must be insulated and requires a 5/8” x

3/4” reducer fitting at the quick disconnect

connections. See Figure 1 below.

Note: Use 5/8” wire to attach the quick disconnects to the other components.