Toshiba VF-nC1 User Manual

Page 54

Advertising
background image

E6581090

E-2

5

☆

The following control input terminals are always operative, no matter how the EOQF parameter
(command mode selection) and the HOQF parameter (frequency setting mode selection) are
set.

 

• Reset terminal (enabled only when a trip occurs.)

 

• Standby terminal

 

• External input trip stop terminal

☆

Before changing the setting of the EOQF parameter (command mode selection) or the HOQF
parameter (frequency setting mode selection), be sure to put the inverter out of operation. (When
H

is set to , the settings of these parameters can be changed even during operation.)

• There are two kinds of functions: function of responding to signals from the device specified with

the HOQF parameter and function of responding to signals from the terminal board only.

• When the highest-priority command is entered from an external device or a terminal board, it

takes priority over commands from the device specified with the HOQF parameter.

HOQF

=0

VI input
PNL/TB:OFF

UP and DOWN keys on
operation panel

HOQF

=1

PNL/TB:ON

VI input
EOQF

: Terminal board

PNL/TB:OFF

Internal potentiometer

HOQF

=2

PNL/TB:ON

VI input
EOQF

: Terminal board

PNL/TB:OFF

Serial communications

HOQF

=3

PNL/TB:ON

VI input
EOQF

: Terminal board

FCHG:OFF
PNL/TB:OFF

Internal potentiometer

FCHG:ON
PNL/TB:OFF

VI input

HOQF

=4

PNL/TB:ON

VI input
EOQF

: Terminal board

5.2

Meter setting and adjustment

HOUN : FM/OUT terminal functions selection
HO : Meter adjustment

• Function

The FM/OUT terminal can be switched between meter output (PWM output) and open
collector. When connecting a meter to the FM/OUT terminal, set the HOUN parameter to a
number other than -1 (open collector output) and connect the meter between FM/OUT
(positive side) and CC (negative side).
If you want to connect a meter to the inverter, choose a full-scale 0~1mAdc ammeter or a
full-scale 0~7.5Vdc-1mA voltmeter.
The meter output of VFNC1 may have some errors because of PWM waveform.

Especially if the meter output is near 0, the errors may be increased.

* To switch between current input and voltage input, use the H parameter

(Analog input / logic input function selection).