E6581090

E-6

5

5.6

Maximum frequency

HJ : Maximum frequency (Hz)

Output frequency (Hz)

When HJ = 80Hz

When HJ = 60Hz

80Hz

60Hz

0              100%   Frequency setting signal (%)

• This function determines the

maximum value in line with the
ratings of the motor and load.

• Maximum frequency cannot be

adjusted during operation. To
adjust, first stop the inverter.

★

If HJ is increased, adjust the upper limit frequency WN as necessary.

■

Parameter setting

Title

Function

Adjustment range

Default setting

HJ

Maximum frequency (Hz)

30.0~200 (Hz)

*

* The value is changed according to the set-up parameter condition.

(VFNC1 (S)-□□□□P□-W type)
80 [Hz] for VFNC1 (S)-□□□□P□-W type.

5.7

Upper limit and lower limit frequencies

WN : Upper limit frequency (Hz)
NN : Lower limit frequency (Hz)

0           100%

Output frequency (Hz)

WN

HJ

Frequency setting signal

★

Signals with a frequency
higher than the frequency set
with WN will not be put out.

Upper limit

frequency

0           100%

Output frequency (Hz)

HJ

NN

Lower limit

frequency

Frequency setting signal

★

The output frequency
cannot be set below the
frequency set with NN.

■

Parameter setting

Title

Function

Adjustment range

Default setting

WN

Upper limit frequency (Hz) 0.5~HJ (Hz)

*

NN

Lower limit frequency (Hz) 0.0~WN (Hz)

0.0

* The value is changed according to the set-up parameter condition.

(VFNC1 (S)-□□□□P□-W type)
80 [Hz] for VFNC1 (S)-□□□□P□-W type.

• Function

1) Programs the range of frequencies output by the inverter (maximum output values).
2) This frequency is used as the reference for acceleration/deceleration time.

• Function

Programs the lower limit frequency that determines the lower limit of the output frequency
and the upper limit frequency that determines the upper limit of that frequency.