Performance data – Trane XV 90 User Manual

Page 7

Advertising
background image

7

Pub. No. 22-1682-05-0802 (EN)

Performance
Data

*UY060R9V3V FURNACE COOLING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER

OUTDOOR

UNIT SIZE

(TONS)

AIRFLOW

SETTING

DIP SWITCH SETTING

EXTERNAL STATIC PRESSURE

SW 1

SW 2

SW 3

SW 4

0.1

0.3

0.5

0.7

0.9

1.5

LOW

(350 CFM/TON)

ON

ON

OFF

ON

CFM

WATTS

575

65

575

90

575

125

550
155

-

NORMAL

(400 CFM/TON)

ON

ON

OFF

OFF

CFM

WATTS

640

70

640

110

640

140

630

175

-

HIGH

(450 CFM/TON)

ON

ON

ON

OFF

CFM

WATTS

700

85

700

125

700

160

700
200

-

2.0

LOW

(350 CFM/TON)

OFF

ON

OFF

ON

CFM

WATTS

700
100

700
130

700
170

700
210

-

NORMAL

(400 CFM/TON)

OFF

ON

OFF

OFF

CFM

WATTS

800
115

800
155

800
200

800
250

-

HIGH

(450 CFM/TON)

OFF

ON

ON

OFF

CFM

WATTS

900
140

900
195

900
240

900
290

-

2.5

LOW

(350 CFM/TON)

ON

OFF

OFF

ON

CFM

WATTS

875
130

875
180

875
230

875
270

-

NORMAL

(400 CFM/TON)

ON

OFF

OFF

OFF

CFM

WATTS

1000

175

1000

235

1000

285

1000

335

900
310

HIGH

(450 CFM/TON)

ON

OFF

ON

OFF

CFM

WATTS

1125

235

1125

295

1125

345

1100

370

925
318

3

LOW

(350 CFM/TON)

OFF

OFF

OFF

ON

CFM

WATTS

1050

195

1050

260

1050

305

1050

350

920
315

NORMAL

(400 CFM/TON)

OFF

OFF

OFF

OFF

CFM

WATTS

1200

275

1200

330

1200

385

1100

385

940
330

HIGH

(450 CFM/TON)

OFF

OFF

ON

OFF

CFM

WATTS

1325

360

1325

425

1300

460

1175

425

1000

365

NOTES: * First letter may be "A" or "T"
1. At continuous fan setting: Heating or Cooling airflows are approximately 50% of selected cooling value.
2. LOW airflow (350 cfm/ton) is COMFORT & HUMID CLIMATE setting;
NORMAL airflow (400 cfm/ton) is typical setting;
HIGH airflow (450 cfm/ton) is DRY CLIMATE setting.

*UY060R9V3V FURNACE HEATING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER

1st Stage Capacity =
2nd Stage Capacity =

37,000
56,000

AIRFLOW

SETTING

DIP SWITCH SETTING

EXTERNAL STATIC PRESSURE

SW 7

SW 8

0.1

0.3

0.5

0.7

0.9

HEATING

1ST

STAGE

LOW

ON

ON

CFM

TEMP. RISE

WATTS

600

57
85

600

57

110

600

57

155

600

57

190

-

MEDIUM LOW

OFF

ON

CFM

TEMP. RISE

WATTS

700

49
90

700

49

130

700

49

175

700

49

210

-

NORMAL **

ON

OFF

CFM

TEMP. RISE

WATTS

775

44

105

775

44

155

775

44

195

775

44

240

-

HIGH

OFF

OFF

CFM

TEMP. RISE

WATTS

870

39

135

870

39

185

870

39

235

870

39

290

-

HEATING

2ND

STAGE

LOW

ON

ON

CFM

TEMP. RISE

WATTS

860

61

140

920

57

200

920

57

245

920

57

300

670

79

245

MEDIUM LOW

OFF

ON

CFM

TEMP. RISE

WATTS

1000

53

190

1000

53

255

1000

53

305

1000

53

340

700

75

255

NORMAL **

ON

OFF

CFM

TEMP. RISE

WATTS

1125

47

250

1125

47

315

1125

47

370

1025

51

355

775

68

285

HIGH

OFF

OFF

CFM

TEMP. RISE

WATTS

1250

42

340

1250

42

405

1250

42

445

1100

48

390

1000

53

355

NOTES:

* First letter may be "A" or "T"
** Factory setting

Advertising