Performance data – Trane XV 90 User Manual

Page 8

Advertising
background image

8

Pub. No. 22-1682-05-0802 (EN)

Performance
Data

TUY080R9V3V FURNACE COOLING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER

OUTDOOR

UNIT SIZE

(TONS)

AIRFLOW

SETTING

(See Notes)

DIP SWITCH SETTING

EXTERNAL STATIC PRESSURE

SW 1

SW 2

SW 3

SW 4

0.1

0.3

0.5

0.7

0.9

2.0

LOW

(350 CFM/TON)

ON

ON

OFF

ON

CFM

WATTS

750

84

750
122

750
154

720
185

710

221

NORMAL

(400 CFM/TON)

ON

ON

OFF

OFF

CFM

WATTS

840
109

840
146

840

181

840
226

820
264

HIGH

(450 CFM/TON)

ON

ON

ON

OFF

CFM

WATTS

940
136

940
177

940
215

940
274

940
318

2.5

LOW

(350 CFM/TON)

OFF

ON

OFF

ON

CFM

WATTS

850
113

850
150

870
200

890
250

890
295

NORMAL

(400 CFM/TON)

OFF

ON

OFF

OFF

CFM

WATTS

960
150

990
200

1000

230

1020

305

1010

350

HIGH

(450 CFM/TON)

OFF

ON

ON

OFF

CFM

WATTS

1080

195

1110

255

1120

315

1120

365

1080

390

3.0

LOW

(350 CFM/TON)

ON

OFF

OFF

ON

CFM

WATTS

1020

175

1020

225

1040

280

1050

330

1050

375

NORMAL

(400 CFM/TON)

ON

OFF

OFF

OFF

CFM

WATTS

1170

240

1180

300

1200

365

1200

415

1130

420

HIGH

(450 CFM/TON)

ON

OFF

ON

OFF

CFM

WATTS

1290

310

1320

410

1350

470

1340

520

1150

440

3.5

LOW

(350 CFM/TON)

OFF

OFF

OFF

ON

CFM

WATTS

1170

250

1190

315

1210

370

1210

435

1100

405

NORMAL

(400 CFM/TON)

OFF

OFF

OFF

OFF

CFM

WATTS

1360

365

1390

445

1400

500

1360

535

1210

475

HIGH

(450 CFM/TON)

OFF

OFF

ON

OFF

CFM

WATTS

1360

355

1390

450

1400

520

1350

535

1180

460

NOTES: Continuous Fan is with Thermostat Fan Switch on and Dip Switches 5 and 6 in the "ON" position.
1. At continuous fan setting: Heating or Cooling airflows are approximately 50% of selected cooling value.
2. LOW airflow (350 cfm/ton) is COMFORT & HUMID CLIMATE setting;
NORMAL airflow (400 cfm/ton) is typical setting;
HIGH airflow (450 cfm/ton) is DRY CLIMATE setting.

TUY080R9V3V FURNACE HEATING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER

1st Stage Capacity =
2nd Stage Capacity =

49,000
73,000

AIRFLOW

SETTING

DIP SWITCH SETTING

EXTERNAL STATIC PRESSURE

SW 7

SW 8

0.1

0.3

0.5

0.7

0.9

HEATING

1ST

STAGE

LOW

ON

ON

CFM

TEMP. RISE

WATTS

800

56

105

800

56

140

800

56

180

800

56

220

800

56

265

MEDIUM LOW

OFF

ON

CFM

TEMP. RISE

WATTS

860

52

115

880

51

165

890

50

215

920

48

265

910

49

320

NORMAL **

ON

OFF

CFM

TEMP. RISE

WATTS

960

46

150

990

45

200

1000

44

230

1020

44

310

1010

44

350

HIGH

OFF

OFF

CFM

TEMP. RISE

WATTS

1080

41

195

1110

40

255

1120

40

315

1120

40

365

1080

41

390

HEATING

2ND

STAGE

LOW

ON

ON

CFM

TEMP. RISE

WATTS

1100

62

205

1100

62

260

1120

61

320

1120

61

370

1090

63

400

MEDIUM LOW

OFF

ON

CFM

TEMP. RISE

WATTS

1210

57

265

1240

55

340

1260

54

410

1260

54

470

1130

61

430

NORMAL **

ON

OFF

CFM

TEMP. RISE

WATTS

1360

50

365

1390

49

445

1400

49

500

1360

50

535

1210

57

475

HIGH

OFF

OFF

CFM

TEMP. RISE

WATTS

1360

50

355

1390

49

450

1400

49

520

1350

51

535

1180

58

465

NOTES:
** Factory setting