8.3. Control of input/output signals from communication

The input terminals, output terminals, analog input and output signals of the inverters can be con-
trolled by communications.

„

Terminal Output Data (FA50)

The

output

terminals on the inverters can be controlled directly by communications.

Before controlling them, select Function Number 38 to 41 in Output Terminal Function Selection
( - , ,). Set data (0 or 1) can be output to the output terminals by
setting data of Bit 0 and Bit 1 of terminal output data (FA50) by communications.

Data construction of Terminal Output Data (FA50)

Bit

Output Terminal Function

0

1

0

Specified data output 1

(Output terminal selection Number : 38, 39)

OFF

ON

1

Specified data output 2

(Output Terminal Selection Number : 40, 41)

OFF

ON

2 to 15

Example : Controlling only Terminal OUT1 by communication

Set “38” (specified data output 1 [positive logic]) in Output Terminal Selection 1 () in
advance and set “0001H” in FA50 to turn Terminal OUT1 on.

BIT15

BIT0

0

0

0 0

0

0 0

0

0 0

0

0 0

0

0 1

„

Analog Output Data (FA51)

The analog terminals on the inverters, such as Terminal FM can be controlled directly by communi-
cations.
Select “18” (communication analog output) in Analog Terminal Connection Selection Parameters
(example: FM terminal connection meter selection []) before controlling them.

Data set in Analog Output Data (FA51) can be output from the selected analog terminal. The data
adjustment range is 0 to 1023 (10bit resolution) . Refer to “Meter Setting and adjustment” in the in-
struction manual for inverters for the complete information.