TROUBLESHOOTING GUIDE

(continued)

Symptom

Possible Cause

Action

Display does not come
on.

Thermostat is not being
powered.

Check if the thermostat is mounted and latched on the

wallplate—mount and latch the thermostat on the
wallplate.

Check if the circuit breaker is tripped—reset the circuit

breaker.

Check if the fuse is blown—replace the fuse.
Check if the system switch at the equipment is in the Off

position—set to the On position.

Check wiring between thermostat and HVAC equipment—

replace any broken wires.

If 24 Vac is present, proceed with troubleshooting.

Temperature setting
does not change
(Example: cannot set the
heating higher or the
cooling lower).

The upper or lower temperature
limits were reached.

Check that the temperature setpoints are:

Heating: 55 to 85

°

F (13 to 29

°

C)

Cooling: 65 to 99

°

F (18 to 37

°

C).