3 ups system installation, 1 preliminary installation information – Thomas & Betts 9395 User Manual

Page 21

Advertising
background image

UPS 225 - 275 kVA

User’s and Installation Guide

1027212
Revision B

21

3 UPS system installation

3.1 Preliminary installation information

WARNING

Installation should be performed only by qualified personnel.

Refer to the following while installing the UPS system:

Chapter 2 for cabinet dimensions, equipment weight, wiring and terminal data, and
installation notes.
Do not tilt the cabinet more than ±10° during installation.
The landing plates are to be removed to add holes as required. Plate material is 16 gauge
steel (1.5 mm/0.06” thick).
If perforated floor tiles are required for ventilation, place them in front of the UPS.

3.2 Unloading the UPS cabinet from the pallet and mechan-

ical installation

The UPS cabinet is bolted to a wooden pallet supported by wood skids. To remove the pallet
and mechanically install the UPS, perform the following procedure:

NOTE

When a line-up-and-match UPS system is ordered together with battery cabinets, the first
battery cabinet is supplied with two cosmetic covers. The UPS cabinet, additional battery
cabinets, and other ancillary cabinets are supplied without cosmetic covers.

NOTE

When a UPS system is ordered together with battery cabinets for standalone installation,
the first battery cabinet is supplied with two cosmetic covers. Additional battery cabinets
are supplied without cosmetic covers. Cosmetic covers must be ordered for the UPS
cabinet and/or other ancillary cabinets.

WARNING

The UPS cabinet is heavy. See Table 2-1 on page 11 for weight of cabinets. If unloading
instructions are not closely followed, the cabinet may cause serious injury.


Advertising