Table 8.9 Changing From Maintenance Bypass to UPS Power Supply

Step Procedure

LCD/LED

Status (After Execution)

1

Same as steps 1-4 in
Section 8.3.1 “Startup”

2

Turn OFF maintenance
bypass AC circuit breaker

52M. *

,

**

,

***

3

Same as steps 5-11 in Section 8.3.1 “Startup”

→Change to UPS power supply complete.

*

During load operation, ALWAYS operate the circuit breakers in the following order:
52C ON

→ 52L ON → 52M OFF

** UPS power supply is disabled when the 52M circuit breaker is in the on state.

*** This operation is different from that displayed in the help message on the screen.

Be sure to perform the operation as described here.